Starting Auto-Tuning

WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or

serious injury. Ensure the areas surrounding the drive, motor and load are clear before proceeding with Auto-Tuning.

WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with

the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.

WARNING! When performing Rotational Auto-Tuning for motor data or PG encoder offset, always uncouple the motor from the

mechanical system (remove ropes from traction sheave). Performing Rotational Auto-Tuning with the mechanical system connected to

the motor can cause hazardous situations, injury to personnel and damage to the equipment.

NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is applied on the load. Ensure the motor can freely spin

before beginning Auto-Tuning. Failure to comply could result in improper operation of the drive.

Enter the required information from the motor nameplate. Press

to proceed to the Auto-Tuning start display.

Note: These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.

Parameter Settings during Induction Motor Auto-Tuning: T1

The T1-

parameters are used to set the Auto-Tuning input data for induction motor tuning.

Note: For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is

complete, change E1-04, Maximum Output Frequency, to the desired value.

T1-01: Auto-Tuning Mode Selection

Sets the type of Auto-Tuning to be used.

Refer to Auto-Tuning for Induction Motors on page 71

for details on the

different types of Auto-Tuning.

Setting 0: Rotational Auto-Tuning
Setting 1: Stationary Auto-Tuning 1
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 4: Stationary Auto-Tuning 2
T1-02: Motor Rated Power

Sets the motor rated power according to the motor nameplate value.

Step

Display/Result

1.

After entering the data listed on the motor nameplate, press

to confirm.

2.

Press

to activate Auto-Tuning. The drive begins by injecting current into the

motor for about 1 min, and then starts to rotate the motor.
Note: The first digit on the display indicates which motor is undergoing Auto-Tuning
(motor 1 or motor 2). The second digit indicates the type of Auto-Tuning being
performed.

3.

Auto-Tuning finishes in approximately one to two minutes.

No.

Parameter Name

Setting Range

Default

T1-01

Auto-Tuning Mode Selection

2 (V/f)

0 to 2, 4 (OLV, CLV)

2 (V/f)

1 (OLV, CLV)

No.

Parameter Name

Setting Range

Default

T1-02

Motor Rated Power

0.00 to 650.00 kW

Determined by o2-04

- A.TUNE -

0.00 Hz/ 0.00A

Tuning Ready ?

DRV

Auto-Tuning

ESC

FWD

Press RUN key

- A.TUNE -

X.XX Hz/ X.XXA

DRV

Tune Proceeding

Rdy

FWD







- MODE -

End

Tune Successful

DRV

FWD

RESET