Es as shown in, Figure 8, It is possible to set – Yaskawa CIMR-LU Drives User Manual

Page 26: Drive, Yea_common, 3 electrical installation

Advertising
background image

3 Electrical Installation

26

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

Figure 9

Figure 8 Drive Standard Connection Diagram (example: CIMR-LU2A0033)

<1> Remove the jumper when installing a DC link choke. Models CIMR-LU2A0085 through 2A0415, 4A0045

through 4A0605, and 5A0032 through 5A0200 come with a built-in DC link choke.

<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an

optional regenerative converter or dynamic braking option.

<3> Set up a thermal relay sequence to disconnect drive main power in the event of an overheat condition on the

dynamic braking option.

<4> Self-cooling motors do not require the same wiring necessary for motors with separate cooling fans.

Shield ground terminal

+

+

DM

DM

H

1

H

2

HC

<10>

R/L1

S/L2

T/L3

Fuse

MC

2MCCB

MB

ON

OFF

THRX

SA

1

2

TRX

MC MA

TRX

Fault relay
contact

Braking resistor unit
Thermal relay trip contact

MC

MC

SA

SA

THRX

ELCB (MCCB)

R

T

S

Three-phase
power supply
200 to 240 V
50/60 Hz

<14>

2MCCB

r1

s1

t1

MC

Wiring sequence should shut off
power to the drive when a fault
output is triggered.

If running from a 400 V power
supply or 600 V power supply, a
step-down transformer is needed
to reduce the voltage to 200 V.

P1

P2

C1

C2

Photo Coupler 1
(During Frequency Output)

Photo Coupler 2
(not used)

Digital output
5 to 48 Vdc
2 to 50 mA

(default setting)

+



+

+

+

Terminals -, +1, +2, B1, B2 are
for connecting options. Never
connect power supply lines to
these terminals

DC link choke

(option)

U

X

Thermal relay

(option)

+



+

+

+

+

U

X

S

1

S

2

S

3

S

4

S

5

S

6

S

7

A

1

A

2

0 V

AC

R

R

S

S



IG

Drive

B

1

1

2

B

2

2 k

Ω

S

8

SC

0 V

FM

AM

AC

E (G)

<1>

<8>

<8>

<9>

<2><3>

+

24 V

+

V

MA

M

1

M

2

MB

MC

Jumper

Braking resistor
(option)

Up command / Stop

External Fault

Fault Reset

Multi-step Speed 1

Not Used

Multi-function

digtial inputs

(default setting)

Sink / Source mode
selection wire jumper
(default: Sink)

Multi-function
analog inputs

Power supply +10.5 Vdc, max. 20 mA

Analog Input 1 (Speed Bias)
-10 to +10 Vdc (20 k

Ω)

Analog Input 2 (Not used)
-10 to +10 Vdc (20 k

Ω)

V

Power supply, -10.5 Vdc, max. 20 mA

MEMOBUS/Modbus

comm. RS485/422

max. 115.2 kBps

Termination resistor

(120

Ω, 1/2 W)

DIP
Switch S2

Fault relay output
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

Multi-function relay output (Brake Release Command)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

Multi-function analog output 1
(Output Speed)
-10 to +10 Vdc (2mA)

Multi-function analog output 2
(Output Current)
-10 to +10 Vdc (2mA)

Main Circuit

Control Circuit

shielded line

twisted-pair shielded line

main circuit terminal

control circuit terminal

M

3

M

4

Multi-function relay output (Motor Contactor Close Command)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

M

5

M

6

Multi-function relay output (Drive Ready)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

SP

SN

FM

+

AM

<7>

Down command / Stop

Multi-step Speed 2

Multi-step Speed 3

FE

SD

NC

a+

a-

b-

z-

b+

z+

IP
IG

IP12

IP5

IG

SG

TB2

A pulse monitor signal

B pulse monitor signal

Z pulse monitor signal

CN3

PG

<4>

<2>

A+
A



B



Z



B+

Z+

TB1

PG

X3

CN5-C

CN5-B

CN5-A

Option card
connector

M

U/T

1

V/T

2

W/T

U/T1

V/T2

W/T3

3

Ground

Cooling fan

<6>

<5>

M

r1

s1

t1

FU

FV

FW

<12>

<13> <14>

<15>

EDM (Safety Electronic Device Monitor)

Safe Disable inputs

<11>

YEA_common