B Parameter Table

176

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

E3: V/f Pattern for Motor 2

These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 7).

E4: Motor 2 Parameters

These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 7).

No.

Name

Description

Setting

E3-04

<31>

<4> Default setting value is dependent on the drive model (o2-04).

<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.

<31> Available in drive software versions PRG: 7012 or later.

Motor 2 Maximum Output
Frequency

These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case,
the setting for E3-08 will be disregarded. Ensure that the four frequencies are set
according to these rules or an oPE10 fault will occur:
E3-09

≤ E3-07 < E3-06 ≤ E3-04

Default: 60.0 Hz
Min: 10.0 Hz
Max: 200.0 Hz

E3-05

<31>

Motor 2 Maximum Voltage

Default:
230.0 V

<9>

Min: 0.0 V
Max: 255.0 V

<9>

E3-06

<31>

Motor 2 Base Frequency

Default: 60.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz

E3-07

<31>

Motor 2 Mid Output
Frequency

Default: 3.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz

E3-08

<31>

Motor 2 Mid Output
Frequency Voltage

Default:

<4> <9>

Min: 0.0 V
Max: 255.0 V

<9>

E3-09

<31>

Motor 2 Minimum Output
Frequency

Default: 1.5 Hz
Min: 0.0 Hz
Max: 200.0 Hz

E3-10

<31>

Motor 2 Minimum Output
Frequency Voltage

Default:

<4> <9>

Min: 0.0 V
Max: 255.0 V

<9>

No.

Name

Description

Setting

E4-01

<4> Default setting value is dependent on the drive model (o2-04).

<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2A0008 to 2A0033, 4A0005 to 4A0018, and 5A0003

to 5A0013 display values in 0.01 A units, while models CIMR-LU2A0047 to 2A0415, 4A0024 to 4A0605, and 5A0017 to 5A0200 display

values in 0.1 A units.

Motor 2 Rated Current

Sets the full load current for motor 2. Automatically set during Auto-Tuning.

Default:

<4>

Min: 10% of drive
rated current
Max:
200% of drive
rated current

<10>

E4-02

Motor 2 Rated Slip

Sets the rated slip for motor 2. Automatically set during Auto-Tuning.

Default:

<4>

Min: 0.00 Hz
Min: 20.00 Hz

E4-03

Motor 2 Rated No-Load
Current

Sets the no-load current for motor 2. Automatically set during Auto-Tuning.

Default:

<4>

Min: 0 A
Min: [E4-01]

<10>

E4-04

Motor 2 Motor Poles

Sets the number of poles of motor 2. Automatically set during Auto-Tuning.

Default: 4
Min: 2
Max: 48

E4-05

Motor 2 Line-to-Line
Resistance

Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.

Default:

<4>

Min: 0.000

Ω

Max: 65.000

Ω

E4-06

Motor 2 Leakage
Inductance

Sets the voltage drop for motor 2 due to motor leakage inductance as a percentage of
rated voltage. Automatically set during Auto-Tuning.

Default:

<4>

Min: 0.0%
Max: 40.0%

E3-05

E3-08

E3-10

E3-09

E3-07

E3-04

Output Voltage (V)

Frequency (Hz)