F: Option Settings

F parameters are used to program the drive for Encoder and PG feedback from the motor and to function with option
cards.

F1: PG Speed Control Card

No.

Name

Description

Setting

F1-01

Encoder 1 Resolution

Sets the encoder resolution (number of pulses per revolution)

Default:

<5>

Min: 1 ppr
Max:
60000 ppr

<34>

F1-02

Operation Selection at PG
Open Circuit (PGo)

0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.

Default: 1
Min: 0
Max: 3

F1-03

Operation Selection at
Overspeed (oS)

0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.

Default: 1
Min: 0
Max: 3

F1-04

Operation Selection at
Deviation

0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.

Default: 3
Min: 0
Max: 3

F1-05

Encoder 1 Rotation
Direction Selection

0: A phase leads B in the up direction
1: B phase leads A in the up direction

Default:

<5>

Min: 0
Max: 1

F1-06

PG 1 Pulse Monitor Output
Division Ratio

Sets the division ratio for the pulse monitor used of the PG option card installed to
connector CN5-C. By setting “xyz”, the division ratio becomes = [(1 + x) / yz]. If only
using the A pulse for one track input, then the input ratio will be 1:1, regardless of
what F1-06 is set to.

Default: 1
Min: 1
Max: 132

F1-08

Overspeed Detection Level Sets the overspeed detection level as a percentage of the maximum output frequency.

Default: 115%
Min: 0%
Max: 120%

F1-09

Overspeed Detection
Delay Time

Sets the time in seconds for an overspeed situation to trigger a fault (oS).

Default: 0.0 s
Min: 0.0 s
Max: 2.0 s

F1-10

Excessive Speed Deviation
Detection Level

Sets the speed deviation detection level as a percentage of the maximum output
frequency.

Default: 10%
Min: 0%
Max: 50%

F1-11

Excessive Speed Deviation
Detection Delay Time

Sets the time in seconds for a speed deviation situation to trigger a fault (dEv).

Default: 0.5 s
Min: 0.0 s
Max: 10.0 s

F1-14

PG Open-Circuit Detection
Time

Sets the time required to trigger a PG Open fault (PGo).

Default: 2.0 s
Min: 0.0 s
Max: 10.0 s

F1-18

dv3 Detection Selection

0: Disabled
n: Sets the number of dv3 situations that may be detected before triggering an actual
dv3 fault.

Default: 10
Min: 0
Max: 10

F1-19

dv4 Detection Selection

0: Disabled
n: Number of pulses that the A and B pulse are reversed that triggers dv4 detection.

Default: 128
Min: 0
Max: 5000

F1-20

PG Option Card
Disconnect Detection 1

0: Disabled
1: Enabled

Default: 1
Min: 0
Max: 1