H3: multi, H3: multi-function analog inputs – Yaskawa CIMR-LU Drives User Manual

Page 186

Advertising
background image

B Parameter Table

186

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

H3: Multi-Function Analog Inputs

No.

Name

Description

Setting

H3-01

Terminal A1 Signal Level
Selection

0: 0 to 10 V
1: –10 to 10 V

Default: 0
Min: 0
Max: 1

H3-02

Terminal A1 Function
Selection

Sets the function of terminal A1.

Default: 0
Min: 0
Max: 1F

H3-03

Terminal A1 Gain Setting

Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.

Default: 100.0%
Min: -999.9%
Max: 999.9%

H3-04

Terminal A1 Bias Setting

Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.

Default: 0.0%
Min: -999.9%
Max: 999.9%

H3-09

Terminal A2 Signal Level
Selection

0: 0 to 10 V
1: –10 to 10 V
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input
signal.

Default: 0
Min: 0
Max: 0

H3-10

Terminal A2 Function
Selection

Sets the function of terminal A2.

Default: 0
Min: 0
Max: 1F

H3-11

Terminal A2 Gain Setting

Sets the level of the input value selected in H3-10 when 10 V is input at terminal A2.

Default: 100.0%
Min: -999.9%
Max: 999.9%

H3-12

Terminal A2 Bias Setting

Sets the level of the input value selected in H3-10 when 0 V is input at terminal A2.

Default: 0.0%
Min: -999.9%
Max: 999.9%

H3-13

Analog Input Filter Time
Constant

Sets a primary delay filter time constant for terminals A1 and A2. Used for noise
filtering.

Default: 0.03 s
Min: 0.00 s
Max: 2.00 s

H3-16

Offset for Terminal A1

Applies an offset to analog input A1. Can be used for zero adjustment of the analog
input.

Default: 0
Min: -500
Max: 500

H3-17

Offset for Terminal A2

Applies an offset to analog input A2. Can be used for zero adjustment of the analog
input.

Default: 0
Min: -500
Max: 500

H3 Multi-Function Analog Input Settings (H3-02 and H3-10)

Setting

<44> Available in drive software versions PRG: 7017 or later.

Function

Description (For when output is 100%)

0

Speed Reference Bias
(value added to input signal when
multiple analog terminals supply the
speed reference)

E1-04 (maximum output frequency)

2

Auxiliary Speed Reference 1
(used as a second speed reference)

E1-04 (maximum output frequency)

3

Auxiliary Speed Reference 2
(used as third speed reference)

E1-04 (maximum output frequency)

E

<44>

Motor Temperature (PTC thermistor
input)

oH3 Alarm detection level: 1.18 V
oH4 Fault detection level: 2.293 V

14

Torque Compensation (load cell
input)

10 V = Motor rated torque

1F

Not used (Through Mode)

Sets this value when the terminal is not used or when using the terminal in the pass-through
mode

.

TOEP_C710616_38F_5_0.book 186 ページ 2013年12月4日 水曜日 午前9時56分