H: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.

H1: Multi-Function Digital Inputs

No.

Name

Description

Setting

H1-03

<19> With the speed reference priority d1-18 is set to 0 or 3, the default settings for parameters H1-03 to H1-07 governing input terminals S3 to S7

are: 24, 14, 3, 4, and 5 respectively. When d1-18 is set to 1 or 2, the default settings for H1-03 to H1-07 become 50, 54, 51, 53, and F

respectively.

Terminal S3 Function
Selection

Assigns a function to the multi-function digital inputs.
Refer to page

182

to page

183

for a description of setting values.

Note: Unused terminals should be set to F.

Default:

<19>

Min: 3
Max: 79

H1-04

Terminal S4 Function
Selection

Default:

<19>

Min: 3
Max: 79

H1-05

Terminal S5 Function
Selection

Default:

<19>

Min: 3
Max: 79

H1-06

Terminal S6 Function
Selection

Default:

<19>

Min: 3
Max: 79

H1-07

Terminal S7 Function
Selection

Default:

<19>

Min: 3
Max: 79

H1-08

Terminal S8 Function
Selection

Default: F
Min: 3
Max: 79

H1 Multi-Function Digital Input Settings

H1-

Setting

Function

Description

3

Multi-Step Speed Reference 1

When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations
of those terminals will create a multi-step speed sequence using the speed references set in d1-01
through d1-08.

4

Multi-Step Speed Reference 2

5

Multi-Step Speed Reference 3

6

Jog reference selection

Closed: Jog frequency reference (d1-17) selected.
The Jog frequency can be used when the speed reference selection is not assigned to input terminals
(b1-01

≠ 1) and the speed reference priority is set to use the multi-step speed reference (d1-18 = 0 or

3).

7

Accel/decel Ramp Selection 1

Used to switch between accel/decel ramp 1 (set in C1-01, C1-02) and accel/decel ramp 2 (set in C1-
03, C1-04).
When combined with another input terminal set for "Accel/Decel ramp 2" (H1-

= 1A), the drive

can also switch between accel/decel ramp 3 (set in C1-05, C1-06) and accel/decel ramp 4 (set in C1-
07, C1-08).

8

Baseblock Command (N.O.)

Closed: No drive output

9

Baseblock Command (N.C.)

Open: No drive output

F

Not Used (Through Mode)

Select this setting when the terminal is not used or when using the terminal in the pass-through
mode. The terminal does not trigger a drive function but can be used as digital input for the
controller the drive is connected to.

14

Fault Reset

Closed: Resets faults if the cause is cleared and the Up/Down command is removed.

15

Fast Stop (N.O.)

Closed: Decelerates to stop at the Fast Stop ramp set to C1-09.

16

Motor 2 Selection

Open: Motor 1(E1-

, E3-

)

Closed: Motor 2 (E2-

, E4-

)

17

Fast Stop (N.C.)

Open: Decelerates to stop at the Fast Stop ramp set to C1-09.

18

Timer Function Input

Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer
function output (H2-

= 12).