Yec_common, C standards compliance – Yaskawa CIMR-LU Drives User Manual

Page 217

Advertising
background image

C Standards Compliance

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

217

St

an

dar

d

s

Co

mplia

nce

C

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of
grounded systems, contact your Yaskawa representative for instructions.

CE Standards Compliance for DC Power Supply Input

To meet CE standards, the following fuses should be installed. For details, refer to

Figure 102

.

Figure 93

Figure 102 Example of DC Power Supply Input (two L1000A drives connected in series)

Note: 1. When connecting multiple drives together, make sure that each drive has its own fuse. If any one fuse blows, all fuses should be

replaced.

2. For an AC power supply, refer to

Standard Connection Diagram on page 25

.

Note: The recommended fuses and fuse holders are made by Fuji Electric.

5A0010

<6>

7.5

12

20

20

35

FWP-70B (70)

5A0013

<6>

10

16

30

25

45

FWP-100B (100)

5A0017

<6>

15

23

40

40

60

FWP-100B (100)

5A0022

<6>

20

31

60

50

90

FWP-125A (125)

5A0027

<6>

25

38

75

60

100

FWP-125A (125)

5A0032

<6>

25-30

33

60

50

90

FWP-175A (175)

5A0041

<6>

40

44

75

75

125

FWP-175A (175)

5A0052

<6>

50-60

54

100

90

150

FWP-250A (250)

5A0062

<6>

50-60

66

125

110

175

FWP-250A (250)

5A0077

<6>

75

80

150

125

225

FWP-250A (250)

5A0099

<6>

100

108

175

175

300

FWP-350A (350)

5A0130

<6>

125

129

250

225

350

FWP-350A (350)

5A0172

<6>

150

158

300

250

400

FWP-600A (600)

5A0200

<6>

200

228

400

350

600

FWP-600A (600)

<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.

<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.

<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.

<4> When using semiconductor fuses, Bussmann FWH and FWP are required for UL compliance. Select FWH for 240 V and 480 V models and

FWP fuses for 600 V models.

<5> Class L fuse is also approved for this rating.

<6> 600 V class drives are not compliant with European Standards.

Drive Model

CIMR-LU

L1000

Nominal

Output Power

HP

AC Drive Input

Amps

MCCB Rating

Amps

<1>

Time Delay

Fuse Rating

Amps

<2>

Non-time

Delay Fuse

Rating Amps

<3>

Bussmann

Semi-conductor Fuse

Rating

(Fuse Ampere)

<4>

M

M

W/ T3

Drive

V/ T2

U/ T1

+1

_

W/ T3

Drive

V/ T2

U/ T1

+1

_

+

_

Fuse

Fuse

DC power supply

(converter)

YEC_common

TOEP_C710616_38F_5_0.book 217 ページ 2013年12月4日 水曜日 午前9時56分

Advertising