Parameter settings during pm motor auto-tuning: t2 – Yaskawa CIMR-LU Drives User Manual

Page 77

Advertising
background image

4 Start-Up Programming & Operation

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

77

S

tart-U

p

Prog

rammin

g

&

Op

er

at

io

n

4

T1-09: Motor No-Load Current

Sets the no-load current for the motor. The default setting displayed is no-load current automatically calculated from the
output power set in T1-02 and the motor rated current set to T1-04. Enter the data listed on the motor test report. Leave
this data at the default setting if the motor test report is not available.

T1-10: Motor Rated Slip

Sets the rated slip for the motor.

The default setting displayed is the motor rated slip for a Yaskawa motor calculated from the output power set in T1-02.
Enter the data listed on the motor test report.

Parameter Settings during PM Motor Auto-Tuning: T2

The T2-

parameters are used to set the Auto-Tuning input data for PM motor tuning.

T2-01: PM Auto-Tuning Mode Selection

Selects the type of Auto-Tuning to be performed.

Refer to Auto-Tuning for Permanent Magnet Motors on page 71

for

details on different types of Auto-Tuning.

Setting 0: Motor Data Input
Setting 1: PM Stationary Auto-Tuning
Setting 2: PM Stationary Stator Resistance Auto-Tuning
Setting 3: Initial Magnet Pole Search Parameters Auto-Tuning
Setting 4: Stationary PG Encoder Offset Auto-Tuning
Setting 10: Rotational PG Encoder Offset Auto-Tuning
Setting 11: Rotational Back EMF Constant Auto-Tuning
Setting 12: Auto-Tuning of PG-E3 Encoder Characteristics
T2-04: PM Motor Rated Power

Specifies the PM motor rated power in kilowatts.

T2-05: PM Motor Rated Voltage

Sets the PM motor rated voltage.

No.

<1> The value will have two decimal places (0.01 A) in the drive models 2A0008 to 2A0033,4A0005 to 4A0018 and 5A0003 to 5A0013 (refer to

Table 55

,

Table 56

and

Table 57

), and one decimal place (0.1 A) in the drive models 2A0047 to 2A0415, 4A0024 to 4A0605 and 5A0017 to

5A0200.

Parameter Name

Setting Range

Default

T1-09

<1>

Motor No-Load Current

0 to [T1-04] A

(Max: 0 to 2999.9)

No.

Parameter Name

Setting Range

Default

T1-10

Motor Rated Slip

0.00 to 20.00 Hz

No.

<1> Setting 12 is available in drive software versions PRG: 7017 or later.

Auto-Tuning of PG-E3 encoder characteristics requires a PG-E3 option with software version 1102 or later. To identify the PG-E3 software

version, refer to the PG-E3 labeling on the option, in the field designated “C/N” (S + four digit number).

Parameter Name

Setting Range

Default

T2-01

PM Auto-Tuning Mode Selection

0 to 4, 10 to 12

<1>

0

No.

Parameter Name

Setting Range

Default

T2-04

PM Motor Rated Power

0.00 to 650.00 kW

Depending on o2-04

No.

Parameter Name

Setting Range

Default

<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives. Multiply value by 2.875 for 600 V class drives.

T2-05

PM Motor Rated Voltage

0.0 to 255.0 V

<1>

200.0 V

<1>

TOEP_C710616_38F_5_0.book 77 ページ 2013年12月4日 水曜日 午前9時56分