Table 51, Refer to, For details – Yaskawa CIMR-LU Drives User Manual

Page 156: 7 option card installation

Advertising
background image

7 Option Card Installation

156

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

Terminal Functions

Table 51 Option Terminal Functions

Setting the PG Encoder Power Supply Voltage

For the PG-X3 Option, set the voltage for the PG encoder power supply using jumper CN3 located on the option.

NOTICE: The positioning of jumper CN3 selects the PG encoder power supply voltage (5.5 V or 12 V). Select the voltage level for the

PG encoder connected to the option and motor. If the wrong voltage is selected, the PG encoder may not operate properly or may

become damaged as a result.

Table 52 Setting the PG Encoder Power Supply Voltage (IP) with Jumper CN3

Wire Gauges and Tightening Torques

Wire gauge and torque specifications are listed in

Table 53

. For simpler and more reliable wiring, use crimp ferrules on

the wire ends. Refer to the option manuals for the wire size and torque specifications of other options.

Table 53 Wire Gauges and Tightening Torques

Terminal Block

Terminal

Function

Description

TB1

<1> A separate UL-listed class 2 power supply is necessary when the PG requires more than 200 mA to operate.

A+

A+ pulse signal input

• Inputs for the A channel, B channel, and Z pulses from the

PG encoder

• Signal level matches RS-422

A–

A– pulse signal input

B+

B+ pulse signal input

B–

B– pulse signal input

Z+

Z+ pulse signal input

Z–

Z– pulse signal input

SD

NC pin (open)

Open connection connectors for use when cable shields
should not be grounded

FE

Ground

Used as the shield ground termination point.

TB2

IP

PG encoder power supply

• Output voltage: 12.0 V ± 5% or 5.5 V ± 5%
• Max. output current: 200 mA

<1>

IG

PG encoder power supply
common

SG

Monitor signal common

• Output signal for monitoring A channel, B channel, and Z

pulses from the PG encoder

• Signal level matches RS-422

a+

A+ pulse monitor signal

a–

A- pulse monitor signal

b+

B+ pulse monitor signal

b–

B- pulse monitor signal

z+

Z+ pulse monitor signal

z–

Z- pulse monitor signal

Voltage Level

5.5 V ± 5% (default)

12.0 V ± 5%

Jumper CN3

Terminal Signal Screw

Size

Tightening

Torque

N m

(lb.in.)

Bare Cable

Crimp Terminals

Wire Type

Applicable

Gauges

mm

2

Recomm.

Gauge

mm

2

Applicable

Gauges

mm

2

Recomm.

Gauge

mm

2

A+, A–, B+,

B–, Z+, Z–,

SD, FE, IP, IG

M2

0.22 to 0.25

(1.95 to 2.21)

0.75

(18 AWG)

Stranded wire:

0.25 to 1.0

(24 to 17 AWG)

Solid wire:

0.25 to 1.5

(24 to 16 AWG)

0.5

(20 AWG)

0.25 to 0.5

(24 to 20 AWG)

Shielded

twisted pair,

etc.

a+, a–, b+,

b–, z+, z–, SG

Shielded

cable, etc.

IP

IG

a+

z+
z−

a−

b−

b+

SG

A+

B+

A−

B−

Z+

SD

FE

Z−

TB1

TB2

CN3

5.5 V 12 V

CN3

5.5 V 12 V