External wiring – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 109

Advertising
background image

86

Wiring Precautions

Section 3-6

Inductive Loads

When an inductive load is connected to I/O, connect a surge suppressor or
diode in parallel with the load as shown below.

Note

Use surge suppressors and diodes with the following specifications.

External Wiring

Observe the following precautions for I/O wiring, power supply wiring, and
power line wiring.

• When multi-conductor signal cable is being used, do not combine I/O

wires and other control wires in the same cable.

• If wiring racks are parallel, allow at least 300 mm between the racks.

• If the I/O wiring and power cables must be placed in the same duct, they

must be shielded from each other using grounded steel sheet metal.

L

IN

COM

OUT

COM

OUT

COM

L

+

Diode

DC input

Relay output or
triac output

Surge suppressor

Relay output or
transistor output

Diode

Surge suppressor specifications

Diode specifications

Resistor: 50

Capacitor: 0.47

µF

Voltage: 200 V

Breakdown voltage: 3 times load voltage min.

Mean rectification current: 1 A

FQM1 I/O wiring

FQM1 power supply and

general control circuit wiring

Power lines

Ground to 100

Ω or less

Low-current cables

Control cables

Control cables

300 mm min.

300 mm min.

FQM1 I/O wiring

FQM1 power

supply and general

control wiring

Power lines

Steel sheet metal

Ground to 100

Ω or less

200 mm min.