1-2 installation in a control panel, Installation in a control panel – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 76

Advertising
background image

53

Installation

Section 3-1

3-1-2

Installation in a Control Panel

The FQM1 must be mounted inside a control panel on DIN Track.

Note

The FQM1 must be mounted on DIN Track. It cannot be mounted with screws.

Wiring Ducts

Use wiring ducts to wire the FQM1’s built-in I/O. Install the wiring ducts to
facilitate wiring the built-in I/O. It is handy to have the duct at the same height
as the FQM1.

Wiring Duct Example

The following example shows the proper installation of wiring ducts.

Note

Tighten terminal block screws and cable screws to the following torques.

Terminal Screws

M4: 1.2 N·m
M3: 0.5 N·m

INPUT

AC100

-240V

L2/N

L1

NC

NC

Duct

Duct

Unit

20 mm min.

20 mm min.

DIN Track

80.0 mm

FQM1

30 mm

40 mm

30 mm

PLC

Mounting
bracket

Duct

Advertising