Note

(1) The inrush current is given for a cold start at room temperature with an

AC power supply. The AC inrush control circuit uses a thermistor element
with a low-temperature current control characteristic. If the ambient tem-
perature is high or the FQM1 is hot-started, the thermistor will not be suf-
ficiently cool, and the inrush currents given in the table may be exceeded
by up to twice the given values. When selecting fuses or breakers for ex-
ternal circuits, allow sufficient margin in shut-off performance. If the
FQM1 is hot-started, the capacitor will not be discharged, and the inrush
currents given in the table may be exceeded by up to twice the given val-
ues.

(2) Disconnect the Power Supply Unit's LG terminal from the GR terminal

when testing insulation and dielectric strength. Testing the insulation and
dielectric strength with the LG terminal and the GR terminals connected
will damage internal circuits.

2-3

Coordinator Module

Nomenclature

Note

Cover the peripheral port and RS-232C port with the supplied covers when
the ports are not being used to prevent dust contamination.

Indicators

FLEXIBLE
MOTION
CONTROLLER

RDY
RUN
ERR

PRPHL

COMM1
COMM2

PERIPHERAL

PORT

ON

OFF

CM001

2

CN1

RS422

1

40

39

1 2

FLEXIBLE
MOTION
CONTROLLER

RDY

RUN

ERR

PRPHL

COMM1
COMM2

ON

OFF

CM001

1 2

Peripheral
port baud rate
detection/System
Setup switch

40-pin connector

㧔24 general-purpose

I/O points and RS-422A

Peripheral
port

RS-232C
port

Coordinator Module

Indicators

Indicator Color

Name

Status

Meaning

RDY

Green Module operation

Lit

The Module is operating normally.

Not lit

Module error (e.g., WDT error).

RUN

Green Program execution Lit

Executing internal Module program.

Not lit

Internal Module program stopped.

ERR

Red

Module error

Lit

Fatal error.

Flash-
ing

Non-fatal error.

Not lit

Module operating normally.