Wiring Precautions

Section 3-6

• The circuit below should NOT be used for I/O devices having a voltage

output.

Precautions when
Connecting a Two-wire DC
Sensor

When using a two-wire sensor with a 24-V DC input device, check that the fol-
lowing conditions have been met. Failure to meet these conditions may result
in operating errors.

1,2,3...

1.

Relation between the FQM1 ON voltage and the sensor residual voltage:

V

ON

≤ V

CC

– V

R

2.

Relation between the FQM1 ON current and sensor control output (load
current):

I

OUT

(min)

≤ I

ON

≤ I

OUT

(max.)

I

ON

= (V

CC

– V

R

– 1.5 [FQM1 internal residual voltage])/R

IN

If I

ON

is smaller than I

OUT

(min), connect a bleeder resistor R. The bleeder

resistor constant can be calculated as follows:

R

≤ (V

CC

– V

R

)/(I

OUT

(min.) – I

ON

)

Power W

≥ (V

CC

– V

R

)

2

/R

× 4 [allowable margin]

IN

7 mA
0 V

+

COM

+

IN

COM

7 mA
0 V

+

IN

COM

0 V

+

+

Output

Output

Output

NPN current output

PNP current output

Voltage output

Sensor
power
supply

Sensor power
supply

Sensor
power
supply

DC input

DC input

DC input

Current
regulator

+

IN

0 V

+

COM

Sensor
power
supply

DC input

Output