Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 37

Advertising
background image

14

Basic Operating Procedure

Section 1-6

Wiring I/O terminals and connectors. Refer to 3-3 Wiring Module Connec-
tors
for details.

3.

Initial Hardware Settings

Set the DIP switch on the front of the Coordinator Module as required. Re-
fer to 2-3 Coordinator Module for details.

4.

Turning ON Power and Checking Initial Operation

Connect the CX-Programmer (using CX-Programmer Ver. 5.0 with the
FQM1 Patch Software installed). Refer to 3-1-4 Connecting FQM1 Com-
ponents
for details.

Check the power supply wiring and voltage and then turn ON the power
supply. Check the RDY indicator and CX-Prorammer display. Refer to 8-2
Connecting the CX-Programmer
for details.

5.

System Setup Settings Using the CX-Programmer

With the FQM1 in PROGRAM mode, change the settings in the System
Setup as necessary from the CX-Programmer online. (Another method is
to change the System Setup in CX-Programmer offline and transfer it to the
Coordinator Module and Motion Control Modules.) Set the Sync Mode un-
der Synchronization between Modules to ASync Mode to make debugging
easier. Refer to System Setup in the Coordinator Module on page 311 in
Appendix C System Setup, Auxiliary Area Allocations, and Built-in I/O Al-
locations
for details.

6.

Writing the Programs

Write the programs for the Coordinator Module and Motion Control Mod-
ules with the CX-Programmer. Refer to Appendix A Programming and to
the FQM1 Instructions Reference Manual (Cat. No. O011) for details.

7.

Transferring the Programs

Transfer the programs from CX-Programmer to the Coordinator Module
and Motion Control Modules.

8.

Testing Operation

a.

Checking I/O Wiring

b.

Trial Operation
Test operation after switching the FQM1 to MONITOR mode.

c.

Monitoring and Debugging
Monitor operation from the CX-Programmer. Use functions such as
force-setting/force-resetting bits, tracing, and online editing to debug
the program.

Note

If the Coordinator and Motion Control Modules are connected at
the same time, set the baud rate to 38.4 kpps max.

9.

Saving and Printing the Programs

Save the debugged ladder programs and System Setup.

10. Running the Programs

Switch the FQM1 to RUN mode to run the programs.

Output wiring

With the FQM1 in PROGRAM mode, force-set output bits
and check the status of the corresponding outputs.

Input wiring

Activate sensors and switches and either check the status
of the input indicators or check the status of the corre-
sponding input bits with the CX-Programmer’s Bit/Word
Monitor operation.

Advertising