5-8 pulse input function description, Pulse input function description, High-speed counter function description – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 176

Advertising
background image

153

Pulse Inputs

Section 7-5

7-5-8

Pulse Input Function Description

The pulse input function uses the high-speed counters. The pulse input func-
tion can be used to monitor changes (movement) in the high-speed counter
PV (mode 1) or changes in the high-speed counter frequency (mode 2).

High-speed Counter Function Description

Input Signal Type and
Count Mode

High-speed counters 1 and 2 support the following inputs. The input method
application depends on the signal type.

Phase Differential Inputs

This method uses the phase Z signal and the two phase signals (phase A and
phase B) for a

Ч1, Ч2, or ×4 phase differential. The count is incremented or

decremented according to the offset between the two phase signals.

Increment/Decrement Pulse Inputs

The phase-A signal is the UP pulse and the phase-B signal is the DOWN
pulse. The count is incremented or decremented by these pulses.

Pulse + Direction Inputs

The phase-A signal is the pulse signal and the phase-B signal is the direction
signal. The count is incremented or decremented based on the ON/OFF sta-
tus of the phase-B signal.

Phase Differential Input Operation

Phase A Phase B

×1 multiplier

×2 multiplier

×4 multiplier

L

Increment

Increment

Increment

H

---

---

Increment

H

---

Increment

Increment

L

---

---

Increment

L

---

---

Decrement

H

---

Decrement

Decrement

H

---

---

Decrement

L

Decrement

Decrement

Decrement

0

Phase A

1

2

3

2

1

2

0

1

2

3

4

5

6

5

4

3

2

1

2

3

4

0

1 2 3 4 5 6 7 8 9 1011 12 1110 9 8 7 6 5 4 3 2

1

2 3 4 5 6 7 8

Phase B

×1 multiplier

×2 multiplier

×4 multiplier