3-3 operating mode changes and i/o memory, 4 power off operation, 4-1 power off operation – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 123: Power off operation, Operating mode changes and i/o memory

Advertising
background image

100

Power OFF Operation

Section 4-4

4-3-3

Operating Mode Changes and I/O Memory

Note

(1) The cycle time will increase by approximately 10 ms when the operating

mode is changed from MONITOR to RUN mode. This will not cause an
error for exceeding the maximum cycle time limit.

(2) In Sync Mode, the Motion Control Module operating mode will change

one cycle after the Coordinator Module operating mode has changed.

4-4

Power OFF Operation

4-4-1

Power OFF Operation

The following processing is performed if FQM1 power is interrupted during
operation. The following power OFF processing will be performed if the power
supply falls below 85% of the minimum rated voltage while in RUN or MONI-
TOR mode.

1,2,3...

1.

The Motion Control Modules and Coordinator Module will stop.

2.

All outputs from all Modules will be turned OFF.

85% of the rated voltage (AC power):
85 V AC for 100 V
170 V AC for 200 V
85 V AC for 100 to 240 V (wide range)

The following processing will be performed if power drops only momentarily
(momentary power interruption).

1,2,3...

1.

The system will continue to run unconditionally if the momentary power in-
terruption lasts less than 10 ms, i.e., the time it takes the minimum rated
voltage at 85% or less to return to 85% or higher is less than 10 ms.

2.

A momentary power interruption that lasts more than 10 ms but less than
25 ms is difficult to determine and a power interruption may or may not be
detected.

3.

The system will stop unconditionally if the momentary power interruption
lasts more than 25 ms.

It thus requires between 10 and 25 ms to detect a power interruption. This
time can be increased by setting the User-set Power OFF Detection Time (0
to 10 ms) in the System Setup.

Note

The User-set Power OFF Detection Time appears in the System Setup simply
as the “Power OFF Detection Time.”

Mode Changes

Cleared areas

Retained areas

• I/O bits
• Data Link bits
• Work bits
• Timer PV

• DM Area
• Counter PV

RUN or MONITOR to
PROGRAM

Cleared (See note 1.)

Retained

PROGRAM to RUN
or MONITOR

Cleared (See note 1.)

Retained

RUN to MONITOR or
MONITOR to RUN

Retained (See note 2.)

Retained