Precautions when using pulse outputs – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 198

Advertising
background image

175

Pulse Outputs

Section 7-6

Note

With ACC(888) and PLS2(887), the acceleration/deceleration rate’s
speed-change cycle can be set to 2ms or 1 ms. Also, the acceleration/decel-
eration rate can be set between 1 Hz and 9.999 kHz. Refer to 7-6-11 Acceler-
ation/Deceleration Rates in ACC(888) and PLS2(887) Instructions
for more
details.

Precautions when
Using Pulse Outputs

Pulses are output according to the clock frequency (20 MHz, 10 MHz, 5 MHz,
2.5 MHz, or 1.25 MHz) specified in the System Setup (Pulse Output/Clock).
The clock signal is divided by an integer dividing ratio to create and output the
output pulse frequency. This means that the actual frequency may not be the
same as the target frequency. Refer to the following information to calculate
the actual frequency.

The following information is used to calculate the output frequency.

Target frequency:
Set by user.

Dividing ratio:
An integer set in the dividing circuit used to generate the output pulses at the
target frequency.

Actual frequency:
The actual frequency that is output as generated by the dividing circuit.

Stop

Stops the pulse
output immedi-
ately.

SPED(88
5) or
ACC(888)
or
PULS(88
6) (Elec-
tronic
Cam Con-
trol)

INI(880)

Stop pulse
output

---

Stops the pulse
output immedi-
ately.

SPED(88
5) or
ACC(888)

SPED(88
5)

Port,
Continu-
ous,
Target fre-
quency = 0

---

Decelerates the
pulse output to a
stop.

SPED(88
5) or
ACC(888)

ACC(888)

Port,
Continu-
ous,
Accelera-
tion/decel-
eration
rate,
Target fre-
quency = 0

---

Mode

Frequency changes

Description

Procedure

Example

Instruc-

tions

Settings

Frequency

Present
frequency

INI executed.

Time

Frequency

Present
frequency

SPED executed.

Time

Frequency

Present
frequency

ACC executed.

Time

Acceleration/
deceleration rate

Target
frequency = 0

Advertising