354 auxiliary area allocations appendix d – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 377

Advertising
background image

354

Auxiliary Area Allocations

Appendix D

A570

00

Adjustment Mode Command
Bits
(Effective only when A575 is
5A5A hex.)

Adjustment
Enable

Analog Input

OFF: Adjustment disabled.
ON: Adjustment enabled.
When one of these bits is turned ON, the
default value (offset or gain value) corre-
sponding to the selected I/O signal range is
transferred to Adjustment Mode Monitor
Area (A572 and A573).

02

Analog Output 1

03

Analog Output 2

07

Adjustment
Mode Specifier

OFF: Offset adjustment
ON: Gain adjustment

12

Adjustment
Value Increment

While this bit is ON, the offset or gain value will be incremented
by one resolution unit each 0.5 ms.

13

Adjustment
Value Decre-
ment

While this bit is ON, the offset or gain value will be decremented
by one resolution unit each 0.5 ms.

14

Adjustment
Value Clear

OFF to ON: Clears the adjustment data to the factory defaults.

15

Adjustment
Value Set

OFF to ON: Reads the present value in the Adjustment Mode
Monitor Area (A572 and A573) and saves this value to flash mem-
ory. This adjustment value will be used for the next normal mode
operation.

A571

00

Adjustment Mode Status

Adjustment
Operation Error

ON when an operational error has been made, such as turning
ON both the Analog Input and Analog Output 2 Adjustment
Enable Bits at the same time.

15

Adjustment
Mode Started

ON during adjustment mode operation (when A575 contains
5A5A hex).

A572

00 to 15 Adjustment Mode Monitor

(Effective only when A575 is
5A5A hex.)

Both Analog
Input and Ana-
log Outputs

Setting Offset Mon-
itor

The values in these
words can be over-
written directly,
without using the
Adjustment Value
Increment/Decre-
ment Bits.

−10 to 10 V: FE0C to

01F4 hex

• 0 to 10 V, 0 to 5 V, 1

to 5 V: FF38 to 00C8
hex

A573

00 to 15

Gain Value Monitor

−10 to 10 V: 1194 to

157C hex

• 0 to 10 V, 0 to 5 V, 1

to 5 V: 0ED8 to 1068
hex

A574

00 to 15

Analog Inputs

Number of Average
Value Samples in
Adjustment Mode

Indicates the number of values to be aver-
aged to obtain the Offset/Gain Value Moni-
tor values in adjustment mode. The number
of samples can be set between 0000 and
0040 hex (0 to 64). Set this parameter
before turning ON the Adjustment Enable
Bit.

A575

00 to 15 Adjustment Mode Password

5A5A hex: Adjustment mode enabled.
Other value: Adjustment mode disabled.

A600

00 to 15 High-speed Counter 1 PV

Range: 8000 0000 to 7FFF FFFF
Note For a Linear Counter, high-speed counter overflows/under-
flows are checked when the PV is read (i.e., when Module inter-
nal I/O is refreshed).

A601

00 to 15

A602

00 to 15 High-speed Counter 2 PV

A603

00 to 15

A604 to
A605

00 to 15 High-

speed
Counter
1

For following
counter modes
• Absolute linear

(CW

−)

• Absolute circular
• Absolute linear

(CW+)

PV of absolute
number of rota-
tions

Contains the number of rotations data (PV) read from the
Encoder when the SEN signal is input to the Servo Driver.
8000 0000 to 7FFF FFFF hex

For following
counter modes
• Linear counter
• Circular counter

Monitor data

• When monitoring counter movements (mode 1), contains the

absolute value of the amount of change in the PV of the high-
speed counter over the specified sampling time as a 8-digit
hexadecimal value (0000 0000 to FFFF FFFF hex).

• When monitoring the counter frequency (mode 2), contains the

frequency of the high-speed counter calculated from the PV of
the high-speed counter between 0 and 7A120 hex (0 and 500
kHz).

Address

Bits

Name