219

Analog Input Functions

Section 7-9

Auxiliary Area

Word

Bits

Function

Settings

Controlled

by

A550

00 to 15

Analog Input PV

Contains the value input from the analog input port
(using either the END refresh or immediate refresh)
in 4-digit hexadecimal.
The PV range depends on the input range:

• 0 to 10 V:

FE70 to 20D0 hex

• 0 to 5 V or 1 to 5 V: FF38 to 1068 hex

−10 to 10 V:

DDA0 to 2260 hex

Motion
Control
Module

A552

00

Analog Input
Status

Analog Input

User Adjustment
Completed

OFF: Not adjusted
ON:

Adjustment completed

01 to 06

Reserved

07

Analog Sampling
Started

OFF: Not started
ON:

Started

08

Factory Adjustment
Data Error

OFF: No Error

ON:

Error

(Checked at startup.)

09

User Adjustment
Data Error

OFF: No Error

ON:

Error
(Checked at startup.)

10 to 14

Reserved

---

15

Analog Input
Status

Analog Input

Analog Sampling
Overlap

OFF: Normal sampling

ON:

The next sampling

operation occurred
before the present
sampling operation
completed.

Motion
Control
Module

A559

01 to 15

Analog Input
Status

Analog Input

Number of Samples Indicates the number of data

samples actually input since
sampling started.

Motion
Control
Module

A560

00 to 15

Analog Out-
put 1 Output
Value

When an END refresh is selected, the 4-digit hexadecimal value set
here by the user is output from analog output port 1.

When immediate refreshing is selected, the 4-digit hexadecimal value
being output from analog output port 1 is stored here for monitoring.
The output value range depends on the output range, as shown below.

• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex

−10 to 10 V: EA84 to 157C hex

Note

1. Set the analog output method (END or immediate refreshing) with the

System Setup’s output method setting. A setting of 0 hex specifies an
END refresh. This setting applies to both analog output 1 and 2.

2. Specify the output range with the output 1 setting.

With imme-
diate
refresh:
Motion
Control
Module

With END
refresh:
User

A561

00 to 15

Analog Out-
put 2 Output
Value

This word has the same settings as the analog output 1 output value
(A560), above. (When an END refresh is selected, set the value to out-
put from analog output port 2. When an immediate refresh is selected,
the output value is stored here for monitoring.)

Note

1. Set the analog output method (END or immediate refresh) with the

System Setup’s output method setting. A setting of 0 hex specifies an
END refresh. This setting applies to both analog output 1 and 2.

2. Specify the output range with the output 2 setting.