6-8 time measurement with the pulse counter, Time measurement with the pulse counter – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 201

Advertising
background image

178

Pulse Outputs

Section 7-6

7-6-8

Time Measurement with the Pulse Counter

The one-shot pulse output function can be used to create a high-precision
pulse counter timer.

To measure time with high-precision, start the timer by executing the
STIM(980) instruction with C1 = 000B or 000C and C2 = 0000, and stop the
timer by executing STIM(980) with C1 = 000B or 000C and C2 = 0001.

The timer’s elapsed time is stored in 8-digit hexadecimal in words A621 and
A620 (pulse output 1) or A623 and A622 (pulse output 2). When the timer
starts, the corresponding words are initialized to 0000 0000 hex and the con-
tent is incremented as time passes. The final value is retained when the timer
stops.

Set the pulse output operation mode to Calculation (time measurement) in
advance in the System Setup, as shown in the following table.

Note

(1) The external pulse output from the port is disabled when this mode is se-

lected.

(2) A pulse output port that is being used as a pulse counter timer cannot be

used for any other pulse output functions.

Word

Bits

Function

Contents

A620

00 to 15

Pulse time
measurement
1

Lower
4 digits

Contains the pulse counter’s time mea-
surement in 8-digit hexadecimal.

The content can range from 0000 0000
to FFFF FFFF hex.

Note These words are refreshed dur-

ing the Motion Control Module’s
I/O refreshing.

A621

00 to 15

Upper
4 digits

A622

00 to 15

Pulse time
measurement
2

Lower
4 digits

These words function just like the
words for pulse time measurement 1,
described above.

A623

00 to 15

Upper
4 digits

Tab page

Function

Details

Pulse Output

Pulse output 1

− Operation mode Calculation (time measurement)

Pulse output 2

− Operation mode

Counting mode
(Time measurement)

Timer start condition

Timer stop condition

Timer started by executing
STIM with C2 = 0000.

Timer stopped by executing
STIM with C2 = 0001.

Timer PV in
A620 and A621
or A622 and A623

Elapsed time

PV reset

PV held

Time