Details on system setup settings, Startup mode, Peripheral port settings – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 348: Rs-232c port settings (host link port)

Advertising
background image

325

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

CX-Programmer: Analog Input/Output Tab Page

Note Analog outputs that are not being used can be disabled to decrease the cycle time.

Details on System Setup Settings

Startup Mode

This setting determines the operating mode that will be used when the power supply to the Coordinator Module
is turned ON.

Note The Coordinator Module will start in RUN mode unless the Startup Mode setting in the System Setup is

enabled.

Peripheral Port Settings

The standard settings are for Host Link Mode, 1 start bit, 7-bit data, even parity, 2 stop bits, and 9,600 baud.
Change the System Setup if any other settings are required.

RS-232C Port Settings (Host Link Port)

The standard settings are for Host Link Mode, 1 start bit, 7-bit data, even parity, 2 stop bits, and 9,600 baud.
Change the System Setup if any other settings are required. If no-protocol communications are to be used, be
sure to change the frame format.

+330 to 331 00 to 15 High-speed

counter 1 (Counter
1)

Absolute offset

8000 0000 to 7FFF FFFF hex
Application origin when using an absolute encoder.

Immediately

+332 to 333 00 to 15 High-speed

counter 2 (Counter
2)

Absolute offset

Same as high-speed counter 1.

Address

Bits

Function

Remarks

When setting is read

+350

00 to 03 Analog I/O

Input method

0 hex: END refresh
1 hex: Immediate refresh (using PRV(881)
instruction)

At power ON

04 to 07

Output method

0 hex: END refresh (Analog value output to
A560 and A561 after executing END(001).)
1 hex: Immediate refresh (using instructions)
(Analog value output when SPED(885) or
ACC(888) is executed.) (A560 and A561 are
used for monitoring.)

+351

00 to 07 Analog input

Input range

00 hex:

−10 to 10 V

01 hex: 0 to 10 V
02 hex: 1 to 5 V (4 to 20 mA)
03 hex: 0 to 5 V

At power ON

+353

00 to 07 Analog output 1

Output range

00 hex:

−10 to 10 V

01 hex: 0 to 10 V
02 hex: 1 to 5 V
03 hex: 0 to 5 V
5A hex: Output disabled (Can be used to
shorten I/O refresh time.) (See note.)

At power ON

08 to 11

Output stop func-
tion

0 hex: Clear
1 hex: Hold
2 hex: Maximum value

+354

00 to 07 Analog output 2

Output range

Same as for analog output 1.

08 to 15

Output stop func-
tion

System Setup mode setting disabled

RUN mode

System Setup mode setting enabled

Program: PROGRAM mode
Monitor: MONITOR mode
Run:

RUN mode

Address

Bits

Function

Remarks

When setting

is read

Advertising