2-5 error tables, Error tables, Cpu errors – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 269: Cpu standby, Fatal errors

Advertising
background image

246

Error Processing

Section 9-2

9-2-5

Error Tables

The following tables show the errors which can occur in the FQM1 and indi-
cate the probable cause of the errors.

Note Always confirm the safety of connected equipment before turning the power

supply OFF or ON.

CPU Errors

If the following LED indicator condition appears during operation (in RUN or
MONITOR mode), it indicates that a CPU error has occurred. The CX-Pro-
grammer cannot be connected if a CPU error has occurred.

If a fatal error occurs, the RDY and ERR indicators will be lit and the RUN indi-
cator will be OFF, but a CX-Programmer can be connected. This difference
can be used to distinguish between a CPU error and other fatal errors.

CPU Standby

If the following LED indicator condition appears when the power is turned ON,
it indicates that the FQM1 is in CPU standby status.

When the FQM1 is turned ON, cyclic servicing starts after the Coordinator
Module recognizes all of the connected Motion Control Modules. Operation
can be started at that point.

If the startup mode is RUN or MONITOR mode, the FQM1 will remain in
standby status until all of the Motion Modules have been recognized..

Fatal Errors

If the following LED indicator condition appears during operation (in RUN or
MONITOR mode), it indicates that a fatal error has occurred..

The fatal error’s error contents will be displayed in the Error Tab in the CX-Pro-
grammer’s Error Window. Determine the cause of the error from the error

Power Supply

Unit Indicators

Module Indicators

POWER

RDY

RUN

ERR

PRPHL

COMM1

COMM2

Lit

OFF

OFF

Lit

---

---

---

Operating

status

Error

name

Error flags

in Auxiliary

Area

Error code

(in A400)

Error con-

tents

Probable cause

Remedy

Stopped

CPU
error

None

None

None

A WDT (watchdog timer)
error occurred in a Module.
(This error does not nor-
mally occur)

Turn the power OFF and
restart. The Module may be
damaged. Contact your
OMRON representative.

Power Supply

Unit Indicators

Module Indicators

POWER

RDY

RUN

ERR

PRPHL

COMM1

COMM2

Lit

OFF

OFF

OFF

---

---

---

Operating

status

Error

name

Error flags

in Auxiliary

Area

Error code

(in A400)

Error con-

tents

Probable cause

Remedy

Stopped

CPU
standby

None

None

None

A Motion Control Module
has not started properly.

Replace the Motion Control
Module.

Power Supply

Unit Indicators

Module Indicators

POWER

RDY

RUN

ERR

PRPHL

COMM1

COMM2

Lit

Lit

OFF

Lit

---

---

---

Advertising