4-2 instruction execution for power interruptions, Instruction execution for power interruptions – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 125

Advertising
background image

102

Power OFF Operation

Section 4-4

Description of Operation

Power OFF will be detected if the 100 to 240 V AC power supply stays below
85% of the minimum rated voltage for the Fixed Power OFF Detection Time
(variable between 10 to 25 ms.)

If the User-set Power OFF Detection Time is set (0 to 10 ms) in the System
Setup, the reset signal will turn ON and the Module will be reset immediately
after the User-set Power OFF Detection Time expires.

4-4-2

Instruction Execution for Power Interruptions

If power is interrupted and the interruption is confirmed when the Coordinator
Module or Motion Control Module is operating in RUN or MONITOR mode, the
instruction currently being executed will be completed and then the Module
will be reset.