160

Pulse Inputs

Section 7-5

7-5-9

Pulse Input Function Procedures

High-speed Counter Procedure

1,2,3...

1.

Determine the Input Mode, reset method, and Numeric Range.

• Counting Speed: 50 kHz or 500 kHz

• Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc-

tion

• Reset method: Phase Z and software reset, or Software reset

• Counter Operation: Circular Counter or Linear Counter

2.

Wire the input.

3.

Make the necessary System Setup settings.

• Counting Speed: 50 kHz or 500 kHz

• Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc-

tion

• Reset: Phase Z and software reset, or Software reset

• Counter Operation: Circular Counter or Linear Counter

• Count Check Method: Target-value Comparison or Range Comparison

4.

If the count check is being used, determine the count check (comparison)
method.

5.

Create the necessary ladder programming.

• Turn ON the High-speed Counter 1 or 2 Start Bit (A610.00 or A611.00)

and start the high-speed counter.

• CTBL(882) instruction: Specifies the port, registers the comparison table,

and starts comparison.

• INI(880) instruction: Specifies the port, changes the PV, and starts com-

parison.

• PRV(881) instruction: Specifies the port and reads the high-speed

counter PV.