Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 64

Advertising
background image

41

Motion Control Modules

Section 2-4

Pulse I/O Specifications

FQM1-MMP21 (Pulse I/O)

Item

Specifications

Pulse
inputs

Number of counters 2

Counter operations

Linear counter and circular counter

Input signals

Two words each for phase A, phase B, and phase Z.

Signal levels

24 V DC, line-driver

Input method

Phase differential

×1

Phase differential

×2

Phase differential

×4

Increment/decrement
Pulse + direction

Counting speed

Voltage

50 k Hz

Line-driver

50 k Hz/500k Hz (phase differen-
tial

× 4, 2 MHz)

Absolute Servo
Driver interfaces

2
SEN output specifications: 5 V PNP output, output
current: 5 mA
When SEN signal is output to Servo Driver, Servo
Driver will transmit the number of encoder's rotations
to this Module. After that, it transmits pulse train cor-
responding to displacement of the number of turns to
the Module.

Pulse
outputs

Number of outputs

2

Output signal

CW/CCW

Signal levels

Line-driver (equivalent to AM26LS31)
Max. output current: 20 mA

Output speed

1 MHz

One-
shot
pulse
outputs

Number of outputs

2

Output type

Open collector (NPN)

Max. switching
capacity

80 mA/5 to 24 V DC

± 10%

Min. switching
capacity

7 mA/5 to 24 VDC

± 10%

Output pulse width

Set time

± 1 µs or 0.1% of set time