Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 363

Advertising
background image

340

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

Address

Bits

Name

Function

Controlled

by

A608

00

High-speed
counter 1 status

Target Compar-
ison In-
progress Flag

OFF: Target value comparison is not being performed for
CTBL(882).

Note This flag is always OFF for range comparison.

ON: Target value comparison is being performed for CTBL(882).
Note Target comparison is continued without interruption once it
has been started (as opposed to range comparison), so this flag
can be used to check whether target comparison is in progress.

Module

01

PV Overflow/
Underflow Flag

OFF: There is no counter overflow or underflow in Linear Counter
Mode. This flag will always be OFF in Circular Counter Mode.
ON: There is a counter overflow or underflow in Linear Counter
Mode. The counter PV will be fixed at the overflow or underflow
limit. This flag will be cleared when the High-speed Counter Start
Bit is turned OFF.

02

Reserved

---

03

Phase Z Input
Reset Flag (ON
for one cycle)

ON for one cycle when the counter PV is reset with the counter
reset method set to a phase Z + software reset.
Note This flag will turn ON for one cycle after the counter PV is
reset if the phase Z signal (reset input) turns ON while the High-
speed Counter Reset Bit (A610.01) is ON.

04

Absolute No. of
Rotations Read
Error Flag

OFF: No error
ON: Error

05

Absolute No. of
Rotations Read
Completed
Flag

OFF: Rotations being read or reading has not been executed.
ON: Reading has been completed (Turned ON when serial recep-
tion of the number of rotations has been completed.)

06

Measuring Flag
(measurement
mode 1 or 2)

OFF: Changes in the counter PV or the counter frequency is not
being measured.
ON: Changes in the counter PV or the counter frequency is being
measured.
In measurement mode 1, this flag will turn ON at the beginning of
the sampling time after the Measurement Start Bit (A610.02) is
turned ON.

Note Valid when Counter Data Display in System Setup is set to
Counter Movements (mode 1) or Frequency (mode 2).

07

High-speed
Counter Oper-
ating Flag

OFF: Counter is not operating.
ON: Counter is operating.

08

Count Latched
Flag

OFF: Count has not been latched.
ON: Latching the count has been completed for the latch input.

09 to 11

Reserved

---

12

Absolute Off-
set Preset
Error Flag

OFF: No error occurred when saving the absolute offset.
ON: An error occurred when saving the absolute offset.

13 to 15

Reserved

---