1-3 assembled appearance and dimensions, Assembled appearance and dimensions – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 77

Advertising
background image

54

Installation

Section 3-1

Routing Wiring Ducts

Install the wiring ducts at least 20 mm away from the FQM1 and any other
objects, (e.g., ceiling, wiring ducts, structural supports, and devices) to pro-
vide enough space for air circulation and replacement of Modules.

3-1-3

Assembled Appearance and Dimensions

The Modules that make up the FQM1 are connected to each other, and an
End Module is connected to the right end.

INPUT

AC100

-240V

L2/N

L1

NC

NC

FQM1

FQM1

FQM1

FQM1

200 mm min.

Input duct

Output duct

Power duct

PLC

Terminal blocks
for power
equipment

Terminal blocks
for FQM1

Fuses, relays, timers, etc.
(NOT heat-generating
equipment, power
equipment, etc.)

Power
equipment
such as
transformers
and
magnetic
relays

Breakers,
fuses

INPUT

AC100

-240V

L2/N

L1

NC

NC

Advertising