2 error processing, 2-1 error categories, 2-2 error information – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 266: Error processing, Error categories, Error information, Indicator status and error conditions

Advertising
background image

243

Error Processing

Section 9-2

9-2

Error Processing

9-2-1

Error Categories

Errors in the FQM1 can be broadly divided into the following three categories.

9-2-2

Error Information

There are basically four sources of information on errors that have occurred:

• The LED indicators on the front of the Coordinator and Motion Control

Modules

• The Auxiliary Area Error Flags

• The Auxiliary Area Error Contents Words

• The Auxiliary Area Error Code Word

Note

When two or more errors occur at the same time, the highest (most serious)
error code will be stored in A400.

Indicator Status and
Error Conditions

The following table shows the status of the FQM1’s indicators for errors that
have occurred in RUN or MONITOR Mode.

Category

Result

Indicators

Comments

RDY

RUN

ERR

Standby

The FQM1 will not start operation
in RUN or MONITOR mode.

OFF

OFF

OFF

This status occurs when a faulty
Motion Control Module is con-
nected.

Non-fatal Errors
(including FAL)

The FQM1 will continue operating
in RUN or MONITOR mode.

ON
(Green)

ON
(Green)

Flashing
(Red)

This status indicates a non-fatal
error other than a communications
error.

Fatal Errors
(including FALS)

The FQM1 will stop operating in
RUN or MONITOR mode.

ON
(Green)

OFF

ON
(Red)

This status indicates a fatal error
other than a power interruption.

(The indicators will all be OFF when
there is a power interruption.)

RDY
RUN
ERR
PRPHL

RDY: Initialization completed

ERR: Self-diagnostic test

Flashing red:
Non-fatal error
Lit red:
Fatal error

COMM1
COMM2

RUN:

PRPHL:

COMM1:

Module Indicators

Lit when the Modules
are in RUN or
MONITOR mode.

Lit yellow when the
Module is communi-
cating through the
peripheral port

Lit yellow when the
Module is commu-
nicating through the
RS-232C port

Flags
indicating
the type of
error.

Words
providing
error
information.

Error Flags

Error Info.

Error Code
Word
(A400)

A400
contains the
error code.
(See note.)

Auxiliary Area Flags and Words

A400

Error code

COMM2:

Lit yellow when the
Module is commu-
nicating through the
RS-422A port

Indicator

CPU error

CPU reset

CPU

standby

Fatal error

Non-fatal

error

Communications error

Peripheral

RS-232C

RS-422A

RDY

OFF

OFF

OFF

ON

ON

ON

ON

ON

RUN

OFF

OFF

OFF

OFF

ON

---

---

---

Advertising