Power OFF Operation

Section 4-4

Note

The above timing chart shows an example when the User-set Power OFF
Detection Time is set to 0 ms.

The following timing chart shows the Coordinator Module power OFF opera-
tion in more detail.

Power OFF Timing Chart

Fixed Power OFF Detection Time

The time it takes to detect power OFF after the power supply falls below 85%
of the minimum rated voltage.

User-set Power OFF Detection Time

The time after power OFF is detected until it is confirmed. This can be set in
the System Setup within a range from 0 to 10 ms (default: 0 ms).

If an unstable power supply is causing power interruptions, set a longer User-
set Power OFF Detection Time (10 ms max.) in the System Setup.

Power Holding Time

The maximum amount of time (fixed at 10 ms) that 5 V will be held internally
after power interruption is detected.

10 ms

25 ms

25 ms

0

0 to 10 ms

Time

10 to 25 ms

Power supply
voltage

Power supply
voltage

Power supply
voltage

Momentary power
interruption not detected
and operation continues.

85% of the rated voltage or less

Operation will continue or stop
depending on whether or not a
momentary power interruption
is detected.

Momentary power
interruption detected
and operation stops.

Reset signal

Stopped

Fixed Power OFF
Detection Time:
Default is 10 to
25 ms (Power OFF
undetermined)

Holding time for 5 V internal
power supply after power
OFF detection: 10 ms.

Power OFF detected

Power OFF confirmed

User-set Power
OFF Detection
Time: 0 to 10 ms
(set in System
Setup)

Operation always stopped at this
point regardless.

Processing time after
power OFF is confirmed:
10 ms minus User-set
Power OFF Detection
Time
Note: The interrupt task
execution time must be
less than or equal to pro-
cessing time after power
OFF is confirmed.

85% of rated
voltage

Power OFF
detected signal

Program execution
status

Cyclic task or interrupt tasks not associated with power OFF

Advertising