Rs-232c port settings for host link – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 338

Advertising
background image

315

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

Baud Rate

RS-232C Port Settings (CX-Programmer: Host Port Tab Page)

RS-232C Port Settings for Host Link

Serial Communications Mode

Format

Baud Rate

Address

Settings

Function

Related flags and

words

When setting is

read

Word

Bits

+145

00 to 07 00 hex: 9,600

06 hex: 9,600
07 hex: 19,200
08 hex: 38,400
09 hex: 57,600
Unit: bit/s
Default: 00 hex

Only settings 00 hex and 06 to 09 hex
can be used in peripheral bus mode.

A412.15 (Peripheral
Port Settings Changing
Flag)

At next cycle (Also
can be changed
with STUP (237).)

Address

Settings

Function

Related flags and

words

When setting is

read

Word

Bits

+160

08 to 11 00 hex: Host Link

05 hex: Host Link
Default: 00 hex

This setting determines whether the
RS-232C port will operate in Host Link
mode or another serial communications
mode. Specify either 00 or 05 for Host
Link Mode.

A410.15 (RS-232C Port
Settings Changing Flag)

At next cycle (Also
can be changed
with STUP (237).)

Address

Settings

Function

Related flags and

words

When setting is

read

Word

Bits

+160

15

0: Default format
1: Custom
Default: 00 hex

The standard settings are for 1 start bit,
7-bit data, even parity, 2 stop bits, and
9,600 baud.

A410.15 (RS-232C Port
Settings Changing Flag)

At next cycle (Also
can be changed
with STUP (237).)

03

0: 7-bit
1: 8-bit
Default: 0

Sets the data length.

02

0: 2 bits
1: 1 bit
Default: 0

Sets the number of stop bits.

00 and
01

00: Even
01: Odd
10: None
Default: 00 hex

Sets the parity.

Address

Settings

Function

Related flags and

words

When setting is

read

Word

Bits

+161

00 to 07 00 hex: 9,600

01 hex: 300
02 hex: 600
03 hex: 1,200
04 hex: 2,400
05 hex: 4,800
06 hex: 9,600
07 hex: 19,200
08 hex: 38,400
09 hex: 57,600
Unit: bit/s
Default: 00 hex

Sets the Host Link baud rate. Set the
Standard/Custom setting to 1 to enable
this setting.

A410.15 (RS-232C Port
Settings Changing Flag)

At next cycle (Also
can be changed
with STUP (237).)

Advertising