323

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

CX-Programmer: Pulse Output Tab Page

+323

00 to 03 High-speed

counter 2 (Counter
2)

Input method

Same as for high-speed counter 1 except that fre-
quency measurement (Counter data to monitor,
bit 00 to 03 of +324: 02 hex) cannot be set for
high-speed counter 2.

At power ON

04 to 07

Reset method

08 to 11

Counting speed

12 to 15

Counter operating
mode (Counter opera-
tion)

+324

00 to 03

Counter data to moni-
tor (Counter data dis-
play)

04 to 15

Reserved

+325

00 to 15

Sampling time (for
mode 1 only)

+326 to 327 00 to 15 High-speed

counter 1 (Counter
1)

Circular maximum
count

Sets the maximum circular counter value.
Range: 0000 0001 to FFFF FFFF hex

Absolute encoder res-
olution

0000 0001 to 0000 FFFF hex

Note Set this value in pulses/rotation according
to the encoder dividing ratio set for the Servo
Driver and the input method multiplier set for the
Module.
Example: If the Servo Driver setting is 1,000 and
the Module setting is x4, set FA0 (4,000).

+328 to 329 00 to 15 High-speed

counter 2 (Counter
2)

Circular maximum
count

Same as for high-speed counter 1.

Absolute encoder res-
olution

+330 to 331 00 to 15 High-speed

counter 1 (Counter
1)

Absolute offset

8000 0000 to 7FFF FFFF hex

+332 to 333 00 to 15 High-speed

counter 2 (Counter
2)

Absolute offset

8000 0000 to 7FFF FFFF hex

Address

Bits

Function

Remarks

When setting is

read

+340

00 to 07 Pulse output 1

Operation mode
(Refer to 7-6-6
Pulse Output
Function Details
.)

00 hex: Relative pulse output
01 hex: Absolute pulse output in linear mode
02 hex: Absolute pulse output in circular mode (See
note.)
03 hex: Electronic cam control in linear mode (See
note.)
04 hex: One-shot pulse output
05 hex: Time measurement using pulse counter
06 hex: Electronic cam control in circular mode (See
note.)

At power ON

08 to 15

Clock

00 hex: 20 MHz

Pulse output frequency: 400 Hz
to 1 MHz

01 hex: 10 MHz

Pulse output frequency: 200 Hz
to 200 kHz

02 hex: 5 MHz

Pulse output frequency: 100 Hz
to 100 kHz

03 hex: 2.5 MHz

Pulse output frequency: 40 Hz
to 50 kHz

04 hex: 1.25 MHz

Pulse output frequency: 20 Hz
to 20 kHz

+341

00 to 07 Pulse output 2

Operation mode

Same as for pulse output 1.

08 to 15

Clock

+342 to 343 00 to 15 Pulse output 1

Circular maximum
count

Sets the maximum circular counter value when the
pulse output mode is set to absolute pulse output in
circular mode or electronic cam control in circular
mode.
Range: 0000 0001 to FFFF FFFF hex (See note.)

+344 to
+345

00 to 15 Pulse output 2

Circular maximum
count

Same as for pulse output 1.

Address

Bits

Function

Remarks