252

Error Processing

Section 9-2

9-2-7

Memory Error Check

9-2-8

Program Error Check

Memory error occurred

ON

OFF

No

Yes

Flash Memory Error Flag

(A403.10) ON?

The internal flash memory's rewrite limit has
been exceeded. Replace the Module.

Was power

interrupted while backing

up memory with the CX-

Programmer?

The power supply was turned OFF during a
memory backup. Transfer the data again.

There was a hardware failure in the internal
memory. Replace the Module.

ON

OFF

ON

OFF

Program error occurred

Task Error Flag

(A405.12) ON?

The called task does not exist. Check the
MSKS instruction that enables the interrupt
task with the corresponding task number.

There isn't an END instruciton in the
program. Add an END instruction.

No END Error Flag

(A405.11) ON?

Turn the power supply OFF and ON again.