Analog Input Functions

Section 7-9

7-9-4

Related Areas and Settings

System Setup

Tab page

Function

Settings

Time when setting

becomes effective

Analog Input/
Output

Both inputs
and outputs

Input
method

0 hex:

END refresh

1 hex:

Immediate refresh (Refresh with PRV(881).)

At power ON and
start of operation

Output
method

0 hex:

END refresh
(Content of A560 and A561 is output as
analog output after execution of END
instruction.)

1 hex:

Immediate refresh
(Analog output when SPED(885) or
ACC(888) is executed. A560 and A561
used for monitoring.)

At power ON and
start of operation

Inputs

Input range

00 hex:

−10 to 10 V

01 hex: 0 to 10 V
02 hex: 1 to 5 V (4 to 20 mA)
03 hex: 0 to 5 V

At power ON

Outputs

Output
range

00 hex:

−10 to 10 V

01 hex: 0 to 10 V
02 hex: 1 to 5 V
03 hex: 0 to 5 V
5A hex: Disable outputs (See note.)

Note Outputs can be disabled to shorten the I/O

refreshing time or reduce the Motion Control
Module’s power consumption.

At power ON

Output stop
function

0 hex:

Clear outputs

1 hex:

Hold outputs

2 hex:

Maximum value

Outputs

Output
range

These parameters have the same settings as output
1, above.

Output stop
function