System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

Address

Bits

Name

Function

Controlled by

A564

00

Analog Output 1

Conversion Enable
Bit

ON: Enables D/A conversion (enables analog output).
OFF: Disables DA conversion (analog values output
according to Output Stop Function specification in Sys-
tem Setup).
Note This bit is cleared when the Modules operating
mode is changed between RUN or MONITOR mode
and PROGRAM mode.

User

01 to 15 Reserved

---

---

A565

00

Analog Output 2

Conversion Enable
Bit

ON: Enables D/A conversion (enables analog output).
OFF: Disables DA conversion (analog values output
according to Output Stop Function specification in Sys-
tem Setup).
Note This bit is cleared when the Modules operating
mode is changed between RUN or MONITOR mode
and PROGRAM mode.

User

01 to 15 Reserved

---

---

A570

00

Adjustment Mode
Command Bits
(Effective only
when A575 is
5A5A hex.)

Adjustment Enable Analog Input

OFF: Adjustment disabled.
ON: Adjustment enabled.
When one of these bits is turned ON,
the default value (offset or gain value)
corresponding to the selected I/O signal
range is transferred to Adjustment
Mode Monitor Area (A572 and A573).

User

01

Reserved

02

Analog Out-
put 1

03

Analog Out-
put 2

04 to 06

Reserved

07

Adjustment Mode
Specifier

OFF: Offset adjustment
ON:

Gain adjustment

08 to 11

Reserved

12

Adjustment Value
Increment

While this bit is ON, the offset or gain value will be
incremented by one resolution unit each 0.5 ms.

13

Adjustment Value
Decrement

While this bit is ON, the offset or gain value will be dec-
remented by one resolution unit each 0.5 ms.

14

Adjustment Value
Clear

OFF to ON: Clears the adjustment data to the factory
defaults.

15

Adjustment Value
Set

OFF to ON: Reads the present value in the Adjustment
Mode Monitor Area (A572 and A573) and saves this
value to flash memory. This adjustment value will be
used for the next normal mode operation.

A571

00

Adjustment Mode
Status

Adjustment Opera-
tion Error

ON when an operational error has been made, such as
turning ON both the Analog Input and Analog Output 2
Adjustment Enable Bits at the same time.

Module

01 to 14

Reserved

15

Adjustment Mode
Started

ON during adjustment mode operation (when A575
contains 5A5A hex).

A572

00 to 15 Adjustment Mode

Monitor
(Effective only
when A575 is
5A5A hex.)

Both Analog Input
and Analog Out-
puts

Setting Off-
set Monitor

The values in
these words
can be over-
written
directly, with-
out using the
Adjustment
Value Incre-
ment/Decre-
ment Bits.

−10 to 10 V: FE0C to

01F4 hex

• 0 to 10 V, 0 to 5 V, 1 to

5 V: FF38 to 00C8 hex

Module/User

A573

00 to 15

Gain Value
Monitor

−10 to 10 V: 1194 to

157C hex

• 0 to 10 V, 0 to 5 V, 1 to

5 V: 0ED8 to 1068 hex

A574

00 to 15

Analog Inputs

Number of
Average
Value Sam-
ples in Adjust-
ment Mode

Indicates the number of values to be
averaged to obtain the Offset/Gain
Value Monitor values in adjustment
mode. The number of samples can be
set between 0000 and 0040 hex (0 to
64). Set this parameter before turning
ON the Adjustment Enable Bit.

User

A575

00 to 15 Adjustment Mode Password

5A5A hex: Adjustment mode enabled.
Other value: Adjustment mode disabled.

User