Pulse Inputs

Section 7-5

Mode 1 Procedure

1,2,3...

1.

Determine the Counting Speed, Input Mode, Reset Method, and Counter
Operation.

• Counting Speed: 50 kHz or 500 kHz

• Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc-

tion

• Reset method: Phase Z and software reset, or Software reset

• Counter Operation: Circular Counter or Linear Counter

2.

Wire the input.

3.

Make the necessary System Setup settings.

• Counter Data Display: Counter movements (mode 1)

4.

Create the necessary ladder programming.

• Turn ON the High-speed Counter 1 or 2 Start Bit (A610.00 or A611.00)

and start the high-speed counter.

• Turn ON the Measurement Start Bit (A610.02 or A611.02).

A601

A600

A603

A602

Pulse input 1

A

B

Z

PRV

HIGH-SPEED
COUNTER PV READ

Read PV.

Count

Refresh PV (once each cycle).

Counter PV

Reset Method

Phase-Z /software reset
Software reset

Refresh PV (immediate refresh).

Pulse input 2

A

B

Z

Port 1
Port 2

(Auxiliary Area)

A

Counter Operation

Circular Counter
Linear Counter

Input Mode

System Setup

Input

Reset

Counter Operation

Counting Speed

Phase differential
Pulse + Direction
Increment/Decrement

System Setup

System Setup

Counting Speed

50 kHz
500 kHz

System Setup

Only when using high-speed
counter interrupts.

Counter Start Bit

Turn ON A610.00 or
A611.00.

CTBL

COMPARISON TABLE LOAD

Register table only.
Register table and
start comparison.

INI

MODE CONTROL

Change PV.
Start/Stop comparison.

Ladder Program

A

Interrupt generated.

Specified Interrupt Task

END

See note.

Target-value comparison interrupt

Check count
(compare).

A

Pattern storage

A613 or A615

15

0

Range Comparison, Bit Pattern Output

CTBL

COMPARISON TABLE LOAD

Perform comparison.

Ladder Program

Range comparison is performed only when
the instruction is executed.