353 auxiliary area allocations appendix d – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 376

Advertising
background image

353

Auxiliary Area Allocations

Appendix D

A559

00 to 15 Number of Analog Samples

Indicates the number of data samples actually input since sam-
pling started.

A560

00 to 15 Analog Output 1 Output Value

When an END refresh is selected, the 4-digit hexadecimal value
set here by the user is output from analog output port 1.
When immediate refreshing is selected, the 4-digit hexadecimal
value being output from analog output port 1 is stored here for
monitoring. The output value range depends on the output range,
as shown below.
• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex

−10 to 10 V: EA84 to 157C hex

Note
1. Set the analog output method (END or immediate refreshing)

with the System Setup’s output method setting. A setting of 0
hex specifies an END refresh. This setting applies to both ana-
log output 1 and 2.

2. Specify the output range with the output 1 setting.

A561

00 to 15 Analog Output 2 Output Value

This word has the same settings as the analog output 1 output
value (A560), above. (When an END refresh is selected, set the
value to output from analog output port 2. When an immediate
refresh is selected, the output value is stored here for monitoring.)
Note
1. Set the analog output method (END or immediate refresh) with

the System Setup’s output method setting. A setting of 0 hex
specifies an END refresh. This setting applies to both analog
output 1 and 2.

2. Specify the output range with the output 2 setting.

A562

00

Analog Output 1 Flags

User Adjustment
Completed

Initial value is 0.
Set to 1 if user performs offset/gain adjustment and Returns to
factory default setting of 0 if adjustment value is cleared.

04

Operating

ON: ON while the analog output is being changed by ACC(888).
OFF: Turned OFF when target value is reached.

08

Output SV Error

ON: ON when the output SV setting is outside of the allowed set-
ting range.
OFF: OFF when the output SV is within range.

12

Factory Adjust-
ment Value
Error

ON: ON when the factory-set data stored in flash memory is
invalid.
OFF: OFF when the factory-set data stored in flash memory is
normal.

14

User Adjustment
Value Error

ON: ON when the user-set adjustment value stored in flash mem-
ory is invalid.
OFF: OFF when the user-set adjustment value stored in flash
memory is normal.

A563

00

Analog Output 2 Flags

User Adjustment
Completed

Same as for Analog Output 1 Flags.

04

Operating

08

Output SV Error

12

Factory Adjust-
ment Value
Error

14

User Adjustment
Value Error

A564

00

Analog Output 1 Conversion Enable Bit

ON: Enables D/A conversion (enables analog output).
OFF: Disables D/A conversion (analog values output according to
Output Stop Function specification in System Setup).
Note This bit is cleared when the Modules operating mode is
changed between RUN or MONITOR mode and PROGRAM
mode.

A565

00

Analog Output 2 Conversion Enable Bit

ON: Enables D/A conversion (enables analog output).
OFF: Disables D/A conversion (analog values output according to
Output Stop Function specification in System Setup).

Note This bit is cleared when the Modules operating mode is
changed between RUN or MONITOR mode and PROGRAM
mode.

Address

Bits

Name

Function