Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 272

Advertising
background image

249

Error Processing

Section 9-2

Non-fatal Errors

If the following LED indicator condition appears during operation (in RUN or
MONITOR mode), it indicates that a non-fatal error has occurred..

The non-fatal error’s error contents will be displayed in the Error Tab in the
CX-Programmer’s Error Window. Determine the cause of the error from the
error message and related Auxiliary Area flags/words and correct the cause of
the error.

Errors are listed in order of importance. When two or more errors occur at the
same time, the more serious error’s error code will be recorded in A400.

Non-fatal Errors

I/O Table
Setting
error

80E0

A401.10: I/O
Setting Error
Flag

More than 5 Modules are connected. Check whether the number of Modules is

incorrect. If the number of Modules is
incorrect, turn OFF the power supply and
correctly connect the Modules.

Cycle
Time
Overrun
error

809F

A401.08: Cycle
Time Too Long
Flag

The cycle time has exceeded the
maximum cycle time (watch cycle
time) set in the System Setup.

Change the program to reduce the cycle
time or change the System Setup’s maxi-
mum cycle time setting.

One way to reduce the cycle time is by
jumping parts of the program that aren’t
being used.

System
FALS error

C101 to
C2FF

A401.06: FALS
Error Flag

FALS has been executed in the pro-
gram.

The error code in A400 will indicate
the FAL number. The leftmost digit of
the code will be C and the rightmost
3 digits of the code will be from 101
to 2FF hex, which correspond to FAL
numbers 001 to 511.

Remove the cause of the user-defined
error indicated by the FAL number.

Error

Error

code (in

A400)

Auxiliary Area

flag and word

data

Probable cause

Possible remedy

Power Supply

Unit Indicators

Module Indicators

POWER

RDY

RUN

ERR

PRPHL

COMM1

COMM2

Lit

Lit

Lit

Flashing

---

---

---

Error

Error

code (in

A400)

Flag and word

data

Probable cause

Possible remedy

System FAL
error

4101 to
42FF

A402.15: FAL
Error Flag

FAL has been executed in program.

The error code in A400 will indicate
the FAL number. The leftmost digit of
the code will be 4 and the rightmost
3 digits of the code will be from 101
to 2FF hex, which correspond to FAL
numbers 001 to 511.

Remove the cause of the user-
defined error indicated by the FAL
number.

System Setup
error

009B

A402.10: Sys-
tem Setup Error
Flag

A409: System
Setup Error
Location

There is a setting error in the Sys-
tem Setup. The location of the error
is written to A409.

Set the correct value in the System
Setup.

Motion Control
Module Moni-
toring error

0300

A402.05: Motion
Control Module
Monitoring Error
Flag

An error occurred during cyclic
refreshing with the Motion Control
Module.

Turn the power OFF and ON again.

Advertising