337

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

A562

00

Analog Output 1
Flags

User Adjustment Com-
pleted

Initial value is 0.
Set to 1 if user performs offset/gain adjustment and
Returns to factory default setting of 0 if adjustment
value is cleared.

Module

01 to 03

Reserved

---

04

Operating

ON: ON while the analog output is being changed by
ACC(888).
OFF: Turned OFF when target value is reached.

05 to 07

Reserved

---

08

Output SV Error

ON: ON when the output SV setting is outside of the
allowed setting range.
OFF: OFF when the output SV is within range.

Note Only for END refresh.

09 to 11

Reserved

---

12

Factory Adjustment Value
Error

ON: ON when the factory-set data stored in flash
memory is invalid.
OFF: OFF when the factory-set data stored in flash
memory is normal.

13

Reserved

---

14

User Adjustment Value
Error

ON: ON when the user-set adjustment value stored
in flash memory is invalid.
OFF: OFF when the user-set adjustment value
stored in flash memory is normal.

15

Reserved

---

A563

00

Analog Output 2
Flags

User Adjustment Com-
pleted

Same as for Analog Output 1 Flags.

01 to 03

Reserved

04

Operating

05 to 07

Reserved

08

Output SV Error

09 to 11

Reserved

12

Factory Adjustment Value
Error

13

Reserved

14

User Adjustment Value
Error

15

Reserved

Address

Bits

Name

Function