Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 359

Advertising
background image

336

System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations

Appendix C

FQM1-MMA21 Motion Control Modules with Analog I/O

Address

Bits

Name

Function

Controlled

by

A550

00 to 15 Analog Input PV

Contains the value input from the analog input port (using either the END
refresh or immediate refresh) in 4-digit hexadecimal.
The PV range depends on the input range:
• 0 to 10 V:

FE70 to 20D0 hex

• 0 to 5 V or 1 to 5 V:

FF38 to 1068 hex

−10 to 10 V:

DDA0 to 2260 hex

Module

A552

00

Analog Input Sta-
tus

User Adjustment Com-
pleted

OFF: Not adjusted
ON: Adjustment completed

01 to 06

Reserved

07

Analog Sampling Started OFF: Not started

ON: Started

08

Factory Adjustment Data
Error

OFF: No Error
ON: Error (Checked at power ON.)

09

User Adjustment Data
Error

OFF: No Error
ON: Error (Checked at power ON.)

10 to 14

Reserved

15

Analog Sampling Overlap OFF: Normal sampling

ON: The next sampling operation occurred before
the present sampling operation completed.

A559

01 to 15 Number of Analog

Samples

Indicates the number of data samples actually input since sampling started.

A560

00 to 15 Analog Output 1

Output Value

When an END refresh is selected, the 4-digit hexadecimal value set here by the
user is output from analog output port 1.
When immediate refreshing is selected, the 4-digit hexadecimal value being out-
put from analog output port 1 is stored here for monitoring. The output value
range depends on the output range, as shown below.
• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex

−10 to 10 V: EA84 to 157C hex

Note
1. Set the analog output method (END or immediate refreshing) with the System

Setup’s output method setting. A setting of 0 hex specifies an END refresh.
This setting applies to both analog output 1 and 2.

2. Specify the output range with the output 1 setting.

With immedi-
ate refresh:
Module
With END
refresh: User

A561

00 to 15 Analog Output 2

Output Value

This word has the same settings as the analog output 1 output value (A560),
above. (When an END refresh is selected, set the value to output from analog
output port 2. When an immediate refresh is selected, the output value is stored
here for monitoring.)
Note
1. Set the analog output method (END or immediate refresh) with the System

Setup’s output method setting. A setting of 0 hex specifies an END refresh.
This setting applies to both analog output 1 and 2.

2. Specify the output range with the output 2 setting.