281

Programming

Appendix A

Programming Precautions

Condition Flags

Using Condition Flags

Condition flags are shared by all instructions, and will change during a cycle depending on results of executing
individual instructions. Therefore, be sure to use Condition Flags on a branched output with the same input
condition immediately after an instruction to reflect the results of instruction execution. Never connect a Condi-
tion Flag directly to the bus bar because this will cause it to reflect execution results for other instructions.

Example: Using Instruction A Execution Results

The same input condition (a) is used for instructions A and B to execute instruction B based on the execution
results of instruction A. In this case, instruction B will be executed according to the Condition Flag only when
instruction A is executed.

If the Condition Flag is connected directly to the left bus bar, instruction B will be executed based on the execu-
tion results of a previous rung if instruction A is not executed.

Note Condition Flags are used by all instruction within a single program (task) but they are cleared when the

task switches. Therefore execution results in the preceding task will not be reflected later tasks.

a

Correct Use

Instruction A

Instruction B

Condition Flag
Example: =

Reflects instruction A
execution results.

LD

a

AN

D

=

Instruction Operand

Mnemonic

Instruction A

Instruction B

Instruction B

Instruction A

Incorrect Use

Preceding rung

Condition Flag
Example: =

Reflects the execution results of
the preceding rung if instruction
A is not executed.