Response time, I/o response time, 293 programming appendix a – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 316: Coordinator module i/o response time

Advertising
background image

293

Programming

Appendix A

Response Time

I/O Response Time

The I/O response time is the time it takes from when an built-in input on a Module turns ON, the data is recog-
nized by the Module, and the user program is executed, up to the time for the result to be output to the built-in
output terminals. The length of the I/O response time depends on the following conditions.

• Timing of input bit turning ON

• Cycle time

Coordinator Module I/O Response Time

Minimum I/O Response Time
The I/O response time is shortest when data is retrieved immediately before I/O refresh of the Coordinator
Module. The minimum I/O response time is the total of the Input ON delay, the Cycle time, and the Output ON
delay.

Maximum I/O Response Time
The I/O response time is longest when data is retrieved immediately after I/O refresh of the Coordinator Mod-
ule. The maximum I/O response time is the total of the Input ON delay, (the Cycle time

× 2), and the Output ON

delay.

Calculation Example
Conditions: Input ON delay:

0.1 ms

Output ON delay:

0.1 ms

Cycle time:

2 ms

Minimum I/O response time = 0.1 ms + 2 ms + 0.1 ms = 2.2 ms

Maximum I/O response time = 0.1 ms + (2 ms

× 2) + 0.1 ms = 4.2 ms

Input

Output

I/O refresh

Cycle time

Cycle time

Input ON delay

Output ON delay

Instruction
execution

Instruction
execution

(Read by
Module)

Minimum I/O
response time

I/O refresh

Input

Output

Cycle time

Cycle time

Input ON delay

Output ON delay

Maximum I/O response time

(Read by
Module)

Instruction
execution

Instruction
execution

Instruction
execution

Advertising