2-9 cycle time overrun error check, 2-10 system setup error check, Cycle time overrun error check – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 276: System setup error check

Advertising
background image

253

Error Processing

Section 9-2

9-2-9

Cycle Time Overrun Error Check

9-2-10 System Setup Error Check

Not cause
of error

The program execution time exceeded the
watch cycle time. Increase the watch cycle
time setting in the System Setup.

Yes

No

Yes

No

No

Yes

Cycle Time Overrun Error

occurred

Is the assumed

cycle time less than the

watch cycle time set in the

System Setup?

Are interrupts

being used?

Is the Max.

Interrupt Processing Time

setting OK?

It is possible that the error occurred
because the interrupt task execution time
was too long.

It is possible that the error occurred
because two or more interrupt tasks were
executed. Check how often interrupt tasks
are executed.

There may be an error in the program.
Check all tasks, particularly instructions that
control loops ,such as the JMP instruction.

#0154 hex (340)

Other value

Set the proecessing mode correctly.

System Setup Error occurred

What is in

the System Setup Error

Location (A406)?

A communications error may have occurred
during the transfer from the CX-Programmer.
Transfer the System Setup again.

Advertising