111

Synchronous Data Refresh

Section 5-4

Note

(1) Addresses are the same for the Coordinator Module and all Motion Con-

trol Modules.

(2) When the synchronous data is one-word data (analog input values, ana-

log output values, built-in I/O, etc.), the other word can be used for gen-
eral-purpose data.

5-4-4

Settings

The following settings must be made beforehand when using the synchronous
data refresh function.

System Setup
(Coordinator Module)

Synchronization between Modules and Sync Cycle Time must be set in the
Coordinator Module's System Setup.

Synchronization between Modules

Sync Cycle Time

When the Sync Cycle Time is specified, all Motion Control Modules will syn-
chronize with the Coordinator Module cycle time in PROGRAM mode. The
specified Sync Cycle Time is enabled in RUN and MONITOR modes, and the
Motion Control Module cycle times will change to the set Sync Cycle Time
when in these modes.

Synchronous data link bits will be broadcast from each Module at the time
specified under Sync Cycle Time.

If an interrupt task 000 is created, it can be used as a regular interrupt task
executed each Sync Cycle Time.

When the Sync Cycle Time is on the default setting, the synchronous data link
bits are broadcast from each Module each Coordinator Module cycle. The
Motion Control Module cycles are synchronous with the Coordinator Module
cycle.

Note

If the Sync Cycle Time Too Long Flag (A404.06) turns ON in the Coordinator
Module, it means that the Motion Control Module cycle time is longer than the
Sync Cycle Time. Either change the Sync Cycle Time or check the Motion
Control Module ladder program and shorten the Motion Control Module cycle
time to less than the Sync Cycle Time.

Sent from Motion
Control Module #4

CIO 0216

00 to 15

Set using upper 2 words of Select Synchronous Data in the System
Setup for Motion Control Module #4.

CIO 0217

00 to 15

CIO 0218

00 to 15

Set using lower 2 words of Select Synchronous Data in the System
Setup for Motion Control Module #4.

CIO 0219

00 to 15

Synchronous Data

Link Bit Areas in

Coordinator and

Motion Control

Modules

Word

address

(See note

1.)

Bits

Method for selecting type of synchronous data

Name

Settings

Default

Description

Auxiliary Area

Flags

Enabled

Module Settings Tab Page

Sync Mode

Sync/Async

Sync

Synchronization
between Modules

---

At power ON

Name

Settings

Default

Description

Auxiliary Area

Flags

Enabled

Module Settings Tab Page

Sync Cycle Time

Default (cycle time)
(0.1 to 10.0 ms)

CM cycle time

Sync cycle time
(unit: 0.1 ms)

A404.06
Sync Cycle Time
Too Long Flag

At power ON