General Specifications

Section 2-2

Note

(1) Disconnect the Power Supply Unit's LG terminal from the GR terminal

when testing insulation and dielectric strength. Testing the insulation and
dielectric strength with the LG and GR terminals connected will damage
internal circuits.

(2) Do not apply more than 600 V when testing the dielectric strength of an-

alog I/O terminals. Applying more than 600 V may damage the internal
elements.

Power Supply Unit Specifications

Item

Specifications

Power Supply Unit

CJ1W-PA205R

CJ1W-PA202

Supply voltage

100 to 240 V AC (wide-range), 50/60 Hz

Operating voltage
and frequency
ranges

85 to 264 V AC, 47 to 63 Hz

Power consumption 100 VA max.

50 VA max.

Inrush current
(See note 1.)

At 100 to 120 V AC:
15 A/8 ms max. for cold start at room temperature

At 200 to 240 V AC:
30 A/8 ms max. for cold start at room temperature

At 100 to 120 V AC:
20 A/8 ms max. for cold start at room temperature

At 200 to 240 V AC:
40 A/8 ms max. for cold start at room temperature

Output capacity

5.0 A, 5 VDC (including supply to Modules)

2.8 A, 5 VDC (including supply to Modules)

0.8 A, 24 VDC

0.4 A, 24 VDC

Total 25 W max.

Total 14 W max.

Output terminal

Not provided.

RUN output

Contact configuration: SPST-NO

Switching capacity:
250 V AC, 2 A (resistive load)
120 V AC, 0.5 A (inductive load)
24 VDC, 2 A (resistive load)
24 VDC, 2 A (inductive load)

Not provided.

Insulation resis-
tance

20 M

Ω min. (at 500 VDC) between AC external and GR terminals (See note 2.)

Dielectric strength

2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals (See note 2.)
Leakage current: 10 mA max.

1,000 V AC 50/60 Hz for 1 min between DC external and GR terminals (See note 1.)
Leakage current: 10 mA max.

Noise immunity

2 kV on power supply line (conforming to IEC61000-4-4)

Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s

2

in X, Y, and Z directions for 80

minutes total (Time coefficient: 8 minutes

× coefficient factor 10 = total time 80 min.) (conforming to

JIS C0040)

Shock resistance

147 m/s

2

3 times each in X, Y, and Z directions (conforming to JIS C0041)

Ambient operating
temperature

0 to 55

°C

Ambient operating
humidity

10% to 90% (with no condensation)

Atmosphere

Must be free from corrosive gases.

Ambient storage
temperature

−20 to 75°C

Grounding

Less than 100

Enclosure

Mounted in a panel.

Weight

5 kg. total max.

Dimensions

80

Ч 90 Ч 65 mm (W × H × D)

45

Ч 90 Ч 65 mm (W × H × D)

Safety measures

Conforms to cULus and EC Directives.