257

Troubleshooting Problems in Modules

Section 9-3

Motion Control Module Errors

Input Errors

Error condition

Probable cause

Remedy

The Motion Control Module’s RUN indicator does
not go ON.

An error in program is causing a
fatal error

Correct program.

Motion Control Module does not operate or does not
operate properly.

The I/O bus is faulty.

Replace the Motion Control
Module.

A particular I/O point does not operate.

Error occurs in 8-point or 16-point units.

A particular I/O point stays ON.

None of a particular Module’s I/O points will go ON.

Error condition

Probable cause

Remedy

None of inputs turn ON.
(Indicators are not lit.)

(1) External input power supply

is not being supplied.

Connect a proper external input
power supply.

(2) The external input power

supply voltage is too low.

Adjust supply voltage to within
proper range.

(3) Terminal block connector is

not making good contact.

Replace terminal block connec-
tor.

None of inputs turn ON.
(Indicators are lit.)

Input circuit is faulty.

Replace the Module.

None of inputs turn OFF.

Input circuit is faulty.

Replace the Module.

A particular input does not turn ON.

(1) Input device is faulty.

Replace the input device.

(2) Input wiring disconnected.

Check input wiring.

(3) Faulty terminal block connec-

tor contact.

Replace terminal block connec-
tor.

(4) External input’s ON time is

too short.

Adjust input device

(5) Faulty input circuit

Replace the Module.

(6) An input bit address is used

in an output instruction.

Correct program.

A particular input does not turn OFF.

(1) Input circuit is faulty.

Replace the Module.

(2) An input bit address is used

in an output instruction.

Correct program.

Input turns ON/OFF irregularly.

(1) External input voltage is low

or unstable.

Adjust external input voltage to
within the proper range.

(2) Malfunction due to noise.

Take protective measures
against noise, such as:
(1) Install surge suppressor.
(2) Install isolating transformer.
(3) Install shielded cables
between the inputs and loads.

(3) Faulty terminal block connec-

tor contact.

Replace terminal block connec-
tor.

Errors occur in 8-point or 16-point blocks, i.e., for the
same common.

(1) Faulty terminal block connec-

tor contact.

Replace terminal block connec-
tor.

(2) Faulty data bus

Replace the Module.

(3) Faulty CPU

Replace the Module.

Input indicator does not light, but input operates nor-
mally.

Faulty indicator or indicator cir-
cuit.

Replace the Module.

Advertising