5 data backup, Data backup, Xxii – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 21: 5data backup, Xxii data backup 5

Advertising
background image

xxii

Data Backup

5

5

Data Backup

The user programs, I/O memories, and other data in the Coordinator Module
and Motion Control Modules is backed up either by a super capacitor or flash
memory, as listed in the following table.

The data backup time of the super capacitor is given in the following table and
shown in the following graph.

Note

1.

The times give above assume that the capacitor is completely charged.
Power must be supply to the FQM1 for at least 20 minutes to completely
charge the capacitor.

2.

The backup time of the super capacitor is reduced as the capacitor ages.
It is also affected by the ambient temperature. Use portion of the DM Area
backed up by the super capacitor only for data that is to be held during mo-

Module

Data

Data backup

Coordinator Module

Error log

RAM with super
capacitor

Motion Control Module

DM Area words D30000 to D32767

Error log

Coordinator Module

User program

System Setup

DM Area words D30000 to D32767

Flash memory

Motion Control Module

User program

System Setup

Temperature

Initial

After 5 years

After 10 years

Ta = 25

°C

101.61 hours
(4.23 days)

96.2 hours
(4.01days)

90.8 hours
(3.78 days)

Ta = 40

°C

26.39 hours
(1.09 days)

15.28 hours

4.16 hours

25

35

45

55

65

75

0

24

48

72

96

120

Ambient temperature (

°C)

Super Capacitor Backup Times

Bac

kup time (h)

25

°C: 96.20 h

25

°C: 101.61 h

40

°C: 26.39 h

Initial value,

40

°C: 4.16 h

25

°C: 90.80 h

40

°C: 15.28 h

After 5 years,

After 10 years