Grounding – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual

Page 84

Advertising
background image

61

Wiring

Section 3-2

Terminal Screws and
Crimp Terminals

The terminals on the Power Supply Unit use M4, self-raising terminal screws.

Note

(1) Use crimp terminals for wiring.

(2) Do not connect bare stranded wires directly to terminals.

(3) Tighten the terminal block screws to a torque of 1.2 N·m.

Use M4 crimp terminals for AC power supplies.

!Caution Tighten AC power supply terminal block screws to a torque of 1.2 N·m. Loose

screws may cause shorts, malfunctions, or fire.

Note

(1) Supply power to all of the Power Supply Units from the same source.

(2) Do not remove the protective label from the top of the Power Supply Unit

until the wiring has been completed. This label prevents wire strands and
other foreign matter from entering the Unit during wiring procedures.

(3) Do not forget to remove the label from the top of the Power Supply Unit

after wiring the Unit. The label will block air circulation needed for cooling.

Grounding

• GR is the ground terminal. To help prevent electric shock, ground this ter-

minal to less than 100

Ω and use special ground wire (minimum cross-

sectional area of 2 mm

2

).

7 mm max.

M4 self-raising terminal screws

Tightening torque 1.2 N

m

20 mm max.

Crimp Terminals for AC Power Supply

POWER

PA205R

DC24V

AC240V

OUTPUT

RUN

INPUT

AC100-240V

L2/N

L1

LG (Noise-filtered neutral terminal)
Ground separately with a resistance of
less than 100

Ω to increase resistance to

noise and to prevent electric shocks.

GR (Ground)
Ground this terminal separately to less
than 100

Ω to prevent electric shock.