Rockwell Automation 1336T FORCE Series B User Manual

Page 114

Advertising
background image

Chapter 4

Startup

4–23

Analog I/O Parameter Configuration:

When you have accomplished the hard wiring of the Analog I/O to the
Standard Adapter Board terminals as was detailed in Chapter 2, it is still
necessary to set up the parameters in the Drive to allow for data flow
between the Adapter Board and the Drive. Each Input/Output has
parameters associated with it as shown in Figure 4.7. Set-Up parameters
are used to program the Standard Adapter Board functions, such as Scale
and Offset. Configuration parameters allow the Standard Adapter Board to
communicate with the Drive, and must be linked to analog inputs and
outputs.

Each analog input and output is associated with a scaling and offset set-up
parameter. These parameters must be adjusted for each analog device.

The Drive works with internal drive units. Each parameter is a 16 bit word,
which allows a range of

±

32767 internal units. The Drive is scaled so that

4096 is equal to one unit of the quantity being regulated. A

±

10V

DC

signal applied to an analog input is converted to a digital value of

±

2048,

providing a total range of 4096. When calibrating analog inputs, a scale
factor is applied to this value, to provide an effective range of

±

32767

16

×

2048. The offset parameter determines the offset in volts, applied to

the raw analog value before the scale factor is applied. This allows you to
shift the range of the analog input by

±

4096 drive units (

±

20 volts).

Figure 4.7.
Analog I/O Links

5–12V Pulse Input

+10V Ref

TB5

1
2
3
4
5
6
7
8
9
10
11
12
13
14

355

356 Offset
357 Scale

358

361

–10V Ref

Common

+

In1

TE

TB6

1
2
3
4
5
6
7
8

370

373

376

+

Pot In put

TE

Main+

Main –

4–20mA Input

TE

+

Analog +

Out 1

+

TE

TE

+

+

395 PPR
396 Edge
397 Scale
398

Offset

399

Standard Adapter

Power
Supply

In1

359 Offset
360 Scale

10V Input

10V Input

In1
In1

362 Offset
363 Scale

Pot Input

mA Input

Pulse Value

In1
In1

371 Offset
372 Scale

Analog Output #1

Analog Output #2

Analog +

Out 2

mA Output

374 Offset
375 Scale

mA Out +

377 Offset
378 Scale

Advertising