Rockwell Automation 1336T FORCE Series B User Manual

Page 234

Advertising
background image

Chapter 6
Troubleshooting

6–22

Inverter Diagnostics Result #1 (parameter 258) and Inverter Diagnostics
Result #2
(parameter 259) contain the results of the transistor diagnostic
tests.

Important: Serious component failures may occur if unverified power

transistor fault conditions are ignored or tests are disabled
before you proceed to run the drive under load.

Inverter Diagnostics Result #1 (parameter 258) is defined as follows:

When this
bit is set (1):

Then:

0

A software fault occurred.

1

No motor is connected, or a bus fuse is open.

2

Phase U and W shorted.

3

Phase U and V shorted.

4

Phase V and W shorted.

5

There are shorted modules.

6

A ground fault occurred.

7

A fault occurred before the short module ran.

8

A hardware overvoltage fault occurred.

9

A hardware desat fault occurred.

10

A hardware ground fault occurred.

11

A hardware phase overcurrent fault occurred.

12

There are open power transistor(s).

13

There are current feedback faults.

Bits 14 and 15 are reserved.