Rockwell Automation 1336T FORCE Series B User Manual

Page 162

Advertising
background image

Chapter 5
Programming Parameters

5–36

Auto Tune Speed
[Auto Tune Speed]

Parameter Number

41

Parameter Type

Sink

Display Units

+/– x.x rpm

Drive Units

4096 @ Base Motor Speed

Factory Default

0.85 x Base Motor Speed

Minimum Value

0.3 x Base Motor Speed

Maximum Value

Base Motor Speed

This parameter is the speed of the motor
during an auto tune velocity motor test,
system test, and system ID measure.
4096 is base speed

VP Desired Bandwidth
[Vel Desired BW]

Parameter Number

43

Parameter Type

Sink

Display Units

x.xx rad/sec

Drive Units

Display units x 100

Factory Default

5.00 rad/sec

Minimum Value

0.01 rad/sec

Maximum Value

100.00 rad/sec

Autotune Status
[Auto Tune Status]

Parameter Number

44

Parameter Type

Source

Display Units

bits

Drive Units

value (of bits)

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

001100000.11111111

Enums:

This parameter specifies the velocity loop
bandwidth requested by the User and
determines the dynamic behavior of the
velocity loop. The maximum value for this
parameter is changed by the drive when a
request is made to update the the velocity
loop gains. The vel loop becomes more
responsive and is able to track a faster
changing vel ref as bandwidth is increased.
System and noise limitations will establish
a practical upper limit however.

This parameter indicates the status of
certain conditions related to the autotune
function. This is a bit–coded parameter
that is not changeable by the user.

VP Damping Factor
[Vel Damp Factor]

Parameter Number

45

Parameter Type

Sink

Display Units

x.x

Drive Units

2048 = 1.0 damping

Factory Default

1.0

Minimum Value

0.5

Maximum Value

3.0

Total Inertia
[Total Inertia]

Parameter Number

46

Parameter Type

Sink

Display Units

x.xx sec

Drive Units

Display units x 100

Factory Default

2.00 sec

Minimum Value

0.01 sec

Maximum Value

655.00 sec

This parameter determines the dynamic
behavior of the velocity loop. The damping
factor influences the amount of overshoot
the velocity loop will exhibit during a tran-
sient.

This parameter represents the time, in se-
conds, for a motor coupled to a load to ac-
celerate from zero to base speed, at rated
motor torque. This parameter is calculated
by the Autotune System Inverter Test.

Bit 8 – 11 = Not Used
Bit 12 = Timeout
Bit 13 = No Trq Lim

Bit 0 = Executing
Bit 1 = Complete
Bit 2 = Fail
Bit 3 = Abort
Bit 4 = Flux Active
Bit 5 = Not Ready
Bit 6 = Not Zero Spd
Bit 7 = Running

Autotune Testpoint Data
[Auto Tune TP]

Parameter Number

47

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

This parameter indicates the value of the
internal location selected by the Autotune
TP Sel parameter, 48.